York YVAA Style A Installation Operation & Maintenance page 20

Air-cooled screw liquid chiller
Table of Contents

Advertisement

SECTION 2 - PRODUCT DESCRIPTION
Louvered/Wire Panels Combination – Louvered pan-
els, painted the same color as the unit, are mounted on
external condenser coil faces. Heavy gauge, welded
wire-mesh panels, coated to resist corrosion, are mounted
around base of machine to restrict unauthorized access.
End Hail Guard – Louvered panels, painted with the
same color as the unit, are installed on the rear of the
unit (opposite end of the control panel) to protect the
exposed condenser from flying debris or hail.
V-Guard Panels – Solid panels, painted the same col-
or as the unit, are installed along the sides of the units
to cover exposed piping within the condenser section
without impacting airflow. These guard panels can be
combined with End Hail Guard option for additional
protection from debris.
Evaporator options
38 mm insulation – Double thickness insulation
provided.
Flange Kit – Provides contractor with the couplings
best suited to tie into the chilled water piping. All
flanges are PN10.
Connection Location – The standard unit configura-
tion is available with fluid inlet connections at rear
(opposite control panel end) of unit. Option available
for front fluid inlet on select configurations.
Water Box Heater – Unless an appropriate freeze pro-
tection fluid is used in the chilled fluid circuit, optional
water box heaters are required if the chiller is exposed
to environments that reach ambient temperatures be-
low 00F (-17.80C). When the water box heaters are
operated along with other required freeze protection
protocols, they assist in protecting the evaporator from
freeze damage in ambient temperatures down to -200F
(-280C). A separate, customer supplied 120 V/60 Hz or
230 V/50 Hz single phase power supply is required to
provide power to the water box heaters. In order to con-
trol the operation of the water box heaters, continuous
power must be provided to the chiller control panel.
See the Application Data section for the requirements
for protection against freeze damage.
20
Controls Options
High Ambient Operation – This provides special
control logic coupled with high airflow fans to permit
high ambient up to 52°C (125°F) operation. Fans are
airfoil type blades with high power motors. This option
may also allow for increased machine capacity, allow-
ing the selection of a smaller chassis to meet specific
capacity requirements.
Building Automation System Interface (Tempera-
ture) – Factory installed option to accept a 4 mA to 20
mA or a 0 VDC to 10 VDC input to allow remote reset
of the Leaving Chilled Liquid Temperature Setpoint.
The setpoint can be positively offset upwards up to
22.2°C (40°F). This option is useful for ice storage or
process applications or for periods where higher chilled
liquid temperatures are adequate for low loads. Avail-
able alone or in combination with BAS Load Limit.
Building Automation System Interface (Load
Limit) – Factory installed option to accept a 4 mA to
20 mA or a 0 VDC to 10 VDC input to allow remote
reset of the Load Limit Setpoint. The setpoint can limit
system demand from 30% to 100%. Available alone or
in combination with BAS Temperature Reset.
E-Link – The optional E-Link gateway provides com-
munication between the equipment and Building Auto-
mation Systems, including BACnet (MS/TP), Modbus,
LON, and N2.
Thermal Storage – Provides special control logic and
modifications to produce leaving chilled brine temper-
atures below 4.4°C (40°F) primarily at times of low
ambient temperatures (night time). Option can be used
to produce ice to supplement cooling and significantly
decrease energy costs. The capability of the chiller is
enhanced by using both ice and chilled water simulta-
neously during times of peak cooling needs.
General options
Flow Switch Accessory – Vapor proof SPDT, NEMA
3R switch, 10.3 barg (150 psig) DWP, -29°C to 121°C
(-20°F to 250°F) with 1 in. NPT (IPS) connection for
upright mounting in horizontal pipe. This flow switch
or equivalent must be furnished with each unit. Field
mounted.
Differential Pressure Switch – This 0.2 barg to 3 barg
(3 psig to 45 psig) range switch, with 1/4 in. NPTE
pressure connections, is an alternative to the paddle-
type flow switch. Field mounted.
Form 201.28-NM1.1
Issue date: 08/06/2021
JOHNSON CONTROLS

Advertisement

Table of Contents
loading

Table of Contents