Table 13 - Real Time Error Numbers For Bas, Sc-Eq Or E-Link Communications Card - York YVAA Style A Installation Operation & Maintenance

Air-cooled screw liquid chiller
Table of Contents

Advertisement

SECTION 7 - OPERATION
The following table shows the real time error numbers
that may be encountered during communication setup
and a description of each.
Table 13 - Real time error numbers for BAS, SC-EQ
or E-Link communications card
Error number
(##)
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
RTC/BRAM INVALID
15
BACNET SETUP FAILED
This data can be read and in some cases modified us-
ing a BACnet, Modbus, or N2 network connection.
The BACnet Name is a 12 character or shorter name
used to identify the data in BACnet. The AI, AV, BI,
and BV columns are indexes used to select the data.
112
Description
The AI, AV, BI, and BV number associated with a
BACnet Name should not be changed. If a value is
not wanted in this table, change the BACnet Name to
SPARE_XX_##. SPARE rows can be used for new
values.
When set to BACnet or N2, communications automati-
cally sets Stop Bit (1) and Parity (None) for port.
When connected using BAS and port is set for BAC-
net, Modbus, or N2, the remote settings will continue
to follow the remote setpoints until the port is changed
to another protocol or DE modifier address is set to -1.
The most current data map information
is listed on the Johnson Controls/YORK
Chiller Equipment Integration website. A
copy of the data map can also be obtained
by contacting a local Johnson Controls
office.
Reboot required (cycle power) after
settings are changed.
Form 201.28-NM1.1
Issue date: 08/06/2021
JOHNSON CONTROLS

Advertisement

Table of Contents
loading

Table of Contents