SECTION 5 - TECHNICAL DATA
Table 9 - Optional three-pass rear inlet/front outlet evaporator
YVAA
A
15.1
15
3
(384)
15.1
16
5
(384)
15.1
17
8
(384)
25.5
18
3
(648)
14.1
19
5
(358)
15.3
19
8
(389)
15.1
20
0
(384)
14.1
21
3
(358)
15.1
21
5
(384)
15.3
21
8
(389)
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales Office for ratings and further information.
78
All dimensions - in. (mm)
B
C
D
26.5
6.8
34.5
(673)
(173)
(876)
26.5
29.2
56.1
(673)
(742)
(1425)
26.5
34.9
70
(673)
(886)
(1778)
25.5
17.7
56.8
(648)
(450)
(1443)
25.5
61.5
56.7
(648)
(1562)
(1440)
26.7
117.3
56.1
(678)
(2979)
(1425)
26.53
1.7
38.1
(674)
(43)
(968)
25.5
61.6
58.8
(648)
(1565)
(1494)
26.5
34.9
70
(673)
(886)
(1778)
26.7
78.9
70.3
(678)
(2004)
(1786)
Water
E- nozzle
chilled water
volume gal
size
(L)
58
5
(220)
58
5
(220)
71
6
(269)
48
5
(182)
48
5
(182)
58
5
(220)
71
6
(269)
48
5
(182)
71
6
(269)
71
6
(269)
Form 201.28-NM1.1
Issue date: 08/06/2021
Minimum
Maximum chilled
water flow rate
flow rate
GPM (L/S)
GPM (L/S)
170 (11)
650 (41)
170 (11)
650 (41)
200 (13)
780 (49)
130 (8)
520 (33)
130 (8)
520 (33)
170 (11)
650 (41)
200 (13)
780 (49)
130 (8)
520 (33)
200 (13)
780 (49)
200 (13)
780 (49)
JOHNSON CONTROLS