York YVAA Style A Installation Operation & Maintenance page 14

Air-cooled screw liquid chiller
Table of Contents

Advertisement

SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY
Refrigerants and oils
Refrigerants and oils used in the unit are generally non-
toxic, non-flammable and non-corrosive, and pose no
special safety hazards. Use of gloves and safety glass-
es is, however, recommended when working on the
unit. The buildup of refrigerant vapor, from a leak for
example, does pose a risk of asphyxiation in confined
or enclosed spaces and attention should be given to
good ventilation.
Use only the refrigerant specifically designated for the
unit. Any other type of refrigerant may cause damage
to the equipment and will void the warranty.
High temperature and pressure cleaning
High temperature and pressure cleaning methods (e.g.
steam cleaning) should not be used on any part of the
pressure system as this may cause operation of the
pressure relief devices. Detergents and solvents, which
may cause corrosion, should also be avoided.
Emergency shutdown
In case of emergency , the control panel is fitted with
an incoming supply circuit breaker with a red and yel-
low handle which can be used as the emergency stop
device. When operated it removes the electrical supply
to the inverter, fans, and control circuit thus shutting
down the unit.
MSDS information
Manufacturer Safety Data Sheets (MSDS) information
can be obtained by calling (800) 451-8346 in the U.S.
or by emailing MSDS@3Ecompany.com. Provide the
product name, manufacturer, part number, and the spe-
cific language required. For additional safety informa-
tion, refer to
https://my.jci.com/sites/BE/NASafety
14
Safety labels
.
Form 201.28-NM1.1
Issue date: 08/06/2021
White symbol on blue background.
For safe operation, read the Instructions
first.
Black symbol on yellow background.
Warning: This machine may start auto-
matically without prior warning.
Black symbol on yellow background.
Warning: Hot surface.
Black symbol on yellow background.
Warning: Safety relief valve may dis-
charge gas or liquid without prior warning.
Black symbol on yellow background.
Warning: Isolate all electrical sources of
supply before opening or removing the
cover, as lethal voltages may exist.
Black symbol on yellow background.
General attention symbol.
Black symbol on yellow background.
Warning: On isolating the supply it may
take up to 300 seconds for the capacitor
voltage to fall below 50 volts.
JOHNSON CONTROLS

Advertisement

Table of Contents
loading

Table of Contents