Refrigerant Removal, Evacuation And Charging A Yvaa Chiller - York YVAA Style A Installation Operation & Maintenance

Air-cooled screw liquid chiller
Table of Contents

Advertisement

SECTION 9 - MAINTENANCE
Refrigerant removal, evacuation and charging
a YVAA chiller
Refrigerant removal
The YVAA utilizes a flooded evaporator. Extreme care
must be taken when removing refrigerant to prevent
damage to the evaporator and the chiller. Carefully
review the following caution before proceeding with
the recommended process.
Incorrect removal of refrigerant will
result in catastrophic freeze damage to
the evaporator and possible additional
damage to other chiller components.
Whenever there is water in the evaporator,
the chilled liquid pumps must be ON and
circulating liquid through the evaporator
above minimum recommended flow rates.
When liquid refrigerant is being removed,
monitor the pressure and do not allow the
pressure to drop below the freeze point
of the chilled liquid flowing through the
evaporator until all liquid refrigerant has
been removed from the evaporator and
only gas remains. Once all liquid has
been removed, the remaining refrigerant
vapor can be removed while allowing the
pressure to drop below the freeze point
with the pump circulating liquid through
the evaporator.
To remove refrigerant from the evaporator, complete
the following steps:
1. Turn the chilled liquid pump ON and ensure the
flow is above the minimum recommended flow.
2. Ensure all manual valves in the system are open.
Open Condenser Drain and Economizer Feed
valves to 100% in the service mode.
3. Connect the recovery unit and a manifold gauge
to the liquid line feeding the eductor. There may
be a valve in the line or a Schrader fitting on the
eductor filter for this purpose.
4. Connect the recovery unit to a recovery cylinder
sitting on an accurate scale. Turn the recovery
unit ON and observe the liquid refrigerant flow-
ing from the line into the cylinder. The flow of
liquid should be obvious.
166
5. Monitor the pressure gauge to ensure that the
pressure does not drop below the freeze point of
the chilled liquid. Throttle the flow as needed with
the manifold gauge valves to prevent pressures
from dropping below the freeze point.
6. Continue to remove the liquid refrigerant while
observing the flow and the pressure. Note the
charge in the system based on the nameplate data
to determine when the charge removal is nearly
complete. Monitor the weight of the recovery
cylinder to determine when the cylinder is full.
Change the cylinder as needed.
7. Continue removing refrigerant until liquid is no
longer observed flowing in the manifold hoses.
8. Once the liquid is removed and no longer visible
in the hose, the remaining gas can be pumped out
with the recovery unit while the pressure is al-
lowed to drop to 0 barg (0 psig).
9. Servicing can now be performed on the system as
needed.
Evacuating a system
To evacuate a system, complete the following steps:
1. Turn the chilled liquid pump ON and ensure the
flow is above the minimum recommended flow.
2. Ensure all manual values are open. Open the Con-
denser Drain (Flash Tank Feed) and Economizer
Valves in the Service Mode to 100%.
3. Connect vacuum hoses to as many points as pos-
sible. Be sure that at least one connection is made
on both the high and low side of the piping. A con-
nection to the evacuation fitting on the compres-
sor is also recommended. Evacuate the system to
a minimum of 500 microns. Close the valves at
the evacuation points and ensure the pressure in
the chiller does not rise more than 50 microns in
10 minutes. Check for leaks if the pressure rises.
Form 201.28-NM1.1
Issue date: 08/06/2021
JOHNSON CONTROLS

Advertisement

Table of Contents
loading

Table of Contents