Figure 5 - Acceptable Minimum Clearances Around And Between Units; Table 2 - Minimum Evaporator Tube Removal Clearance - York YVAA Style A Installation Operation & Maintenance

Air-cooled screw liquid chiller
Table of Contents

Advertisement

SECTION 4 - INSTALLATION
Recommended minimum clearances
Recommended clearances for the YVAA units are:
• Side to wall – 6 ft (1.8 m)
• Rear to wall – 6 ft (1.8 m)
• Control panel end to wall – 4 ft (1.2 m)
• Top – no obstructions whatsoever
• Distance between adjacent units – 10 ft (3 m)
A
Tube Removal
Clearance Area
B
A
1.8 m (6
ft)
Minimum
1.2 m (4 ft)
Control panel
Minimum
Figure 5 - Acceptable minimum clearances around
and between units
Clearance dimensions provided in
Figure 5 on page 36 and Table 2 on
page 36 are necessary to maintain good
airflow and ensure correct unit opera-
tion. It is also necessary to consider ac-
cess requirements for safe operation and
maintenance of the unit and power and
control panels. Local health and safety
regulations, or practical considerations
for service replacement of large compo-
nents, may require larger clearances than
those recommended.
36
Tube Removal
C
Clearance Area
3 m (10
ft)
Minimum

Table 2 - Minimum evaporator tube removal clearance

Model YVAA
Frame Cond Evap
in.
015
3
B
26
016
5
B
26
017
8
C
26
018
3
A
26
019
5
A
26
019
8
B
26
020
0
C
26
021
3
A
26
021
5
C
26
021
8
C
26
023
3
B
26
024
5
C
26
024
8
C
26
026
3
B
26
027
0
D
26
027
3
D
26
027
5
E
26
027
8
E
26
029
5
E
26
030
3
C
26
030
5
E
26
030
8
E
26
031
8
E
26
032
3
E
26
033
3
C
26
034
3
E
26
034
5
E
26
036
8
J
26
037
3
F
26
037
5
J
26
039
8
J
26
041
3
H
26
042
5
H
26
042
8
J
26
044
3
G
26
047
5
J
26
048
3
G
26
049
0
K
26
050
0
J
26
052
3
J
26
Form 201.28-NM1.1
Issue date: 08/06/2021
Tube removal
clearance dimensions
A
B
C
mm
in.
mm
in.
mm
663
36
914 132 3353
663
36
914 132 3353
663
36
914 156 3962
663
36
914 144 3658
663
36
914 144 3658
663
36
914 144 3658
663
36
914 156 3962
663
36
914 156 3962
663
36
914 156 3962
663
36
914 156 3962
663
36
914 132 3353
663
36
914 156 3962
663
36
914 156 3962
663
36
914 132 3353
663
36
914 192 4877
663
36
914 192 4877
663
36
914 192 4877
663
36
914 192 4877
663
36
914 192 4877
663
36
914 156 3962
663
36
914 156 3962
663
36
914 156 3962
663
36
914 192 4877
663
36
914 192 4877
663
36
914 156 3962
663
36
914 192 4877
663
36
914 192 4877
663
36
914 192 4877
663
36
914 144 3658
663
36
914 192 4877
663
36
914 192 4877
663
36
914 192 4877
663
36
914 144 3658
663
36
914 192 4877
663
36
914 144 3658
663
36
914 192 4877
663
36
914 144 3658
663
36
914 192 4877
663
36
914 192 4877
663
36
914 192 4877
JOHNSON CONTROLS