Virtual Services Platform 9012 chassis
Situation
Raised floors versus non-
raised floors for cooling
Adjacent equipment
Blocked cooling modules
Clearance
October 2015
Considerations
If you do not have raised floors for cooling you need to ensure air is injected into
the cool intake at the left side. You can add extra stand alone fans to ensure air
enters the chassis.
Consider hot airflow from other pieces of equipment in the vicinity of the Virtual
Services Platform 9012. Computers, Telecommunications, and other equipment
located above and below the Virtual Services Platform 9012 can discharge hot
air onto the chassis.
Placement of the Virtual Services Platform 9012 near walls or placement of
exterior items for cable management can decrease the capacity of the cooling
modules. For instance, the following diagram shows how cable management
blocks two out of four fans in a row. As a result, the cooling module can only
offer 50 per cent of the cooling airflow.
Figure 19: Cable management cooling modules
Diagram
1
2
Do not place the Virtual Services Platform 9012 chassis directly against a wall,
equipment, or other obstruction. Avaya recommends 36 inches (91 centimeters)
of free space in both the front and back of the machine and 6 inches (15.2
centimeters) on each side). However, dependent on circumstances, increase
the space at the side of the Virtual Services Platform 9012 to improve airflow.
Installing the Avaya VSP 9000
Comments on this document? infodev@avaya.com
Description
Cable management blocking fans
Fans