Seismic Requirements; Anchor Requirements; Hurricane Requirements - Trane Climate Changer TCFS Nstallation, Operation, And Maintenance

Table of Contents

Advertisement

Seismic Requirements

Air handling equipment manufactured by Trane is capable
of structurally and operationally withstanding the seismic
response criteria as required by the International Building
Codes (IBC) 2000,2003, 2006, 2009, 2012, and CBC 2007,
2010. Trane has third-party certification for IBC compliance
for seismic applications.
Note: If seismic isolation has been specified, the
following requirements must be adhered to for
installation. Failure to follow these instructions
would void the warranty.

Anchor Requirements

1. Single wide<164 inches – grade to roof mounted
(0<=Sds<=1.85) non-isolated:
a. On 4000 psi concrete:
• 3/4-in. dia. Hilti Kwik bolt TZ carbon steel
concrete anchors at 24 in. o.c.
• 4 3/4-in. min. anchor embedment
• 9-in. min. distance to the nearest edge
• 8-in. min. concrete slab thickness
b. On steel dunnage/steel curb:
• 3/4-in. dia ASTM A325 or SAE grade 5 bolts at 24
in. o.c.
or
• 1-in. long 3/16-in. welds at 24 in. o.c.
2. Stacked single-wide<164 in. – grade to roof mounted
(0<=Sds<=1.85) non-isolated:
a. On 4000 psi concrete:
• 3/4-in. dia. Hilti Kwik bolt TZ carbon steel
concrete anchors at 24 in. o.c.
• 4 3/4-in. min. anchor embedment
• 9-in. min. distance to the nearest edge
• 8-in. min. concrete slab thickness
b. On steel dunnage/steel curb:
• 3/4-in. dia. ASTM A325 or SAE grade 5 bolts at 24
in. o.c.
or
• 1-in. long 3/16-in. welds at 24 in. o.c.
3. Double-wide 164 in. - 328 in. – grade to roof mounted
(0<=Sds<=1.85) non-isolated:
a. On 4000 psi concrete:
• 3/4-in. dia. Hilti Kwik bolt TZ carbon steel
concrete anchors at 24 in. o.c.
• 4 3/4-in. min. anchor embedment
• 9-in. min. distance to the nearest edge
• 8-in. min. concrete slab thickness
b. On steel dunnage/steel curb:
CLCH-SVX010A-EN
Component Installation Requirements
• 3/4-in. dia. ASTM A325 or SAE grade 5 bolts at 24
in; o.c.
or
• 1-in. long 3/16-in. welds at 24 in. o.c.
4. Stacked double-wide 164 in. - 328 in. – grade to roof
mounted (0<=Sds<=1.85) non-isolated:
a. On 4000 psi concrete:
• 3/4-in. dia. Hilti Kwik bolt TZ carbon steel
concrete anchors at 24 in. o.c.
• 4 3/4-in. min. anchor embedment
• 9-in. min. distance to the nearest edge
• 8-in. min. concrete slab thickness
b. On steel dunnage/steel curb:
• 3/4-in. dia ASTM A325 or SAE grade 5 bolts at 24
in. o.c.
or
• 1-in. long 3/16-in. welds at 24 in. o.c.
5. Ultra wide 328 in. - 600 in. – grade to roof mounted
(0<=Sds<=1.85) non-isolated:
a. n 4000psi Concrete:
• 3/4-in. dia. Hilti Kwik bolt TZ carbon steel
concrete anchors at 24 in. o.c.
• 4 3/4-in. min. anchor embedment
• 12-in. min. distance to the nearest edge
• 14-in. min. concrete slab thickness
b. On steel dunnage/steel curb:
• 3/4-in. dia ASTM A325 or SAE grade 5 bolts at 24
in. o.c.
or
• 2 1/2-in. long 3/16-in. welds at 24 in. o.c.
Anchor selection meets or exceeds IBC 2000, 2003, 2006,
and 2009 compliance requirements.
Special inspection per IBC Section 1704 is required on all
installations. All anchors listed above must be installed to
meet compliance.

Hurricane Requirements

Miami/Dade Co. Hurricane Certification
Performance Climate Changer air handlers are approved
and have has been designed to comply with the High
Velocity Hurricane Zone of the Florida Building Code.
Notice of compliance and additional product construction
details can be found at the Miami-Dade County, Building
Code Compliance Office Web site.
The Florida licensed engineer or architect-of-record for the
project shall be responsible for the design, sizing, and
structural adequacy of the product framework as well as
curbing and attachment to the roof, or as accepted by the
corresponding building departments.
31