Pre-Installation Requirements

The T-Series air handler typically ships as a complete air handler, but if shipping splits
are required, it can ship in individual sections, or in section sub-assemblies. Unit sizes
3 to 100 have an integral base rail.
The specifications provided in
shipment. If either the maximum weight or maximum length is exceeded, the T-Series
unit will ship in multiple pieces.
Note: These limits are based on a four-point lift.
Table 1. Shipping length and weight limitations for single piece shipments

Inspection Checklist

Upon receipt of the air-handling unit, prior to unloading, visually check the components
for any damage that may have occurred during shipment. Conduct a thorough inspection
immediately before accepting the shipment.
Note: Delivery cannot be refused. Trane is not responsible for shipping damage.
10
Unit Size
Max Weight (lbs)
3-40
50
57-66
80
100
Check all access doors to confirm the latches and hinges are not damaged.
Inspect the interior of each section for any internal damage.
Concealed damage must be reported within 15 days of receipt.
Inspect the coils for damage to the fin surface and/or coil connections.
If the unit was ordered with factory-mounted controls, locate all sensors.
Items that cannot be factory-mounted should ship inside the control enclosures, or
should be packaged inside the fan or mixing box section.
Check all control devices attached to the unit exterior and confirm they are not
damaged.
Manually rotate the fan wheel to ensure free movement of the shaft, bearings, and
drive.
Inspect the fan housing for any foreign objects.
If the unit shipped in sub-assemblies, locate the assembly hardware, which should be
packaged and shipped inside the fan or mixing box section.
Table 1
indicate the maximum values for a single-piece
15,000
15,000
15,000
15,000
15,000
T-Series Climate Changer Air Handler • CLCH-SVX06A-EN
Max Length (in)
360
336
112
120
124