Trane Climate Changer TCFS Nstallation, Operation, And Maintenance page 50

Table of Contents

Advertisement

Piping and Connections
Figure 58. Dual-circuit condensing unit: evaporator coil with eight distributors
with Horizontal-Split (Standard) Circuiting
Suction line
Suction line
Distributor
Suction lines
Evaporator Coil with Intertwined Circuiting
Distributor
50
Evaporator Coil
Thermal expansion
valves (TXV)
Sight
glass
Filter drier
"Trim"
solenoid valve
"Pump-down"
solenoid valve
Thermal expansion
valves (TXV)
"Trim"
solenoid valve
Sight
glass
"Pump-down"
solenoid valve
1. Pitch the liquid line slightly—1 inch/10 feet —so
that the refrigerant drains toward the
evaporator.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction
Liquid line
(Circuit 2)
header toward the suction riser— 1 inch/10 feet
in the direction of flow. Use the tube diameter
that matches the suction-header connection.
4. This looks like a trap, but is actually due to the
requirement that the refrigerant gas leaving the
coil flows downward, past the lowest suction-
header outlet, before turning upward. Use the
Liquid line
double-elbow configuration to isolate the TXV
(Circuit 1)
bulb from other suction headers.
5. Use the "horizontal" tube diameter as specified
in the condensing unit application manual.
6. Use the tube diameter recommended for a
vertical rise as specified in the condensing unit
application manual. Ensure that the top of the
riser is higher than the evaporator coil.
7. Pitch the suction line slightly—1 inch/10 feet —
so that the refrigerant drains toward the
evaporator.
8. Insulate the suction line.
9. The top of the Circuit 1 suction riser must be
higher than the bottom evaporator coil. Use the
tube diameter recommended for a vertical rise
Liquid line
as specified in the condensing unit application
(Circuit 2)
manual.
10. The top of the Circuit 2 suction riser must be
higher than the top evaporator coil. Use the tube
Liquid line
diameter recommended for a vertical rise as
(Circuit 1)
specified in the condensing unit application
manual.
Filter drier
11. Only use a "trim" solenoid valve for constant-
volume, humidity-sensitive applications. For all
other applications, install a single solenoid
valve (the "pumpdown" solenoid valve)
between the liquid-line filter drier and the sight
glass.
Note: Due to reduced coil volume in condensing
units with microchannel heat exchanger
condenser, do not use trim solenoid valves
for these units.
CLCH-SVX010A-EN