Bell Mouth Discharge Connections; Traq Damper Connections - Trane Climate Changer TCFS Nstallation, Operation, And Maintenance

Table of Contents

Advertisement

Component Installation Requirements
have a framed opening that can be used to secure the duct
to the frames. If the duct is lined, it is important the
insulation does not obstruct the opening of the section.
For a discharge plenum with field-cut openings, attach the
duct to the side panel.

Bell Mouth Discharge Connections

Round duct connections to be fastened to plenum fan and
discharge plenum sections with bell mouth discharge
openings should be sized to attach to the casing or directly
Figure 44. Securing round duct to casing over bell mouth Figure 45. Securing round duct to bell mouth outlet
1 inch
Bell mouth
outlet -
nominal
diameter
1 inch
Round duct
Angle ring

Traq Damper Connections

Size the duct connections to attach to the specified portion
on the face of the mixing box that the duct connection
completely covers all of the Traq damper.
Figure 46. Traq damper duct connections
Traq damper
mixing box
36
Airflow
W
D
H
D = 1 hydraulic duct diameter = 2 x W x H
to the bell mouth fitting. Attachment to the casing requires
the round duct diameter to be sized two inches larger than
the nominal bell mouth outlet. An angle ring with a flat
flange should be affixed to the round duct to secure the
duct to the casing (see
mouth fitting requires the duct and fitting to be insulated
by the installing contractor up to the bell mouth radius to
prevent condensation (see
fitting extends through the casing by one inch.
1 inch
Bell mouth
outlet -
nominal
diameter
Round
duct
1 inch
External
insulation
For a mitered corner, provide one hydraulic duct diameter
between the entering face of the Traq dampers and the
duct turn. For a radius elbow, or sweep, place the elbow
directly against the face of the Traq dampers (see
Figure
46).
Traq damper
mixing box
Mitered
corner
W + H
Figure
44). Attachment to the bell
Figure
45). The bell mouth
Airflow
Radius elbow
(sweep)
CLCH-SVX010A-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Climate changer tcpa

Table of Contents