Piping and Connections
Figure 47.
Drain pan trapping for negative and positive pressure applications
Section under negative pressure
L = H + J + pipe diameter where:
H = 1 inch for each inch of negative
pressure plus 1 inch with loaded filters
J = 1/2 H

Steam Coil Piping

Air handlers fitted with steam coils have labeled holes for
piping penetrations.
Figure 48
coil piping configuration. See
system components in these figures.
The coil condensate return line must be piped full size of
the condensate trap connection, except for a short nipple
screwed directly into the coil header's condensate return
tapping. Do not bush or reduce the coil return trapping
size.
Table 1.
Code of system components for piping figures
Code
System component
FT
Float and thermostatic steam trap
GV
Gate valve
OV
Automatic two-position (ON-OFF) control valve
VB
Vacuum breaker
ST
Strainer
AV
Automatic or manual air vent
MV
Modulating control valve
38
L
illustrates a typical steam
Table 1
for the codes of
Section under positive pressure
L = H + J + pipe diameter where:
H = 1/2 inch (minimum)
J = 1/2 inch plus the unit positive static
pressure at coil discharge (loaded filters)
Figure 48. Typical piping for Type NS steam coils and
horizontal tubes for horizontal airflow
12 in. min.
ST
FT
FT
ST
Full size of
steam trap
connection
H
J
MV
GV
ST
VB
GV
Full size of
coil connection
VB
GV
Full
ST
size
of
main
FT
12 in. min.
CLCH-SVX010A-EN