Routine Maintenance
CDQ Belt Tension
1. Disconnect all power to the desiccant wheel.
2. Slip belt off of drive pulley.
3. Hold the belt with tabs facing outward as shown in
Figure
88, twist tab and push through one link.
Figure 88. Hold belt with tabs facing outward
4. Twist the next tab and push through the two links as
shown in
Figure
89.
Figure 89. Twist and push through links
74
5. Remove one link.
6. Reconnect the belt as shown in
a. Push tab through
b. Align belt
c. Flex second tab through
Figure 90. Reconnect the belt
CDQ Seal Adjustment
Neoprene brush seals are located on both sides of the
cassette around the wheel perimeter and the center
diameter posts. The seals are designed to come in contact
with the wheel and require no maintenance other than
adjustment. The seals consist of a metal and neoprene clip
that grips to the metal posts or panels. These clips can be
manually adjusted.
Figure 91. Seals are located around wheel perimeter
and center of diameter posts
Perimeter seals
Diameter
seals
Figure