Parameter Reference
8.2 SETUP (2.)
UNIT (2.5.4.3.)
Engineering unit to be displayed with the output value.
Options
DECIMAL POINT (2.5.4.4.)
Read only. The number of digits to display after the decimal point (fixed to one).
8.2.5.5
OUTPUT SCALING (2.5.5.)
Scales the Process Variable. The function block parameter OUT SCALE contains the values
of the lower limit and upper limit effective range in AIFB1 units.
LOWER VALUE (2.5.5.1.)
Factory setting:
Setting range:
Purpose:
UPPER VALUE (2.5.5.2.)
Factory setting:
Setting range:
Purpose:
138
m, cm, mm, ft, in, %, Not Used, Unknown, Special
*
%
0%
Range: -999999 to 999999
Defines the operational lower range value of the output value in AIFB1
units.
100%
Range: -999999 to 999999
Defines the operational upper range value of the output value in
AIFB1 units.
LR560 (FOUNDATION FIELDBUS)
Operating Instructions, 06/2018, A5E34648692-AE