Operation Troubleshooting - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters (foundation fieldbus)
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

10.3

Operation troubleshooting

Operating symptoms, probable causes, and resolutions.
Symptom
Display shows
Display shows
Display shows
Display shows
Reading does not
change, but the level
does
Measurement is con-
sistently off by a con-
stant amount
Screen blank
Reading erratic
Reading response
slow
LR560 (FOUNDATION FIELDBUS)
Operating Instructions, 06/2018, A5E34648692-AE
Cause
level or target is out of range
material build-up on antenna
location or aiming:
poor installation
flange not level
Auto False Echo Suppression
may be incorrectly applied
antenna malfunction:
temperature too high
physical damage
SITRANS LR560 processing
wrong echo, for example, vessel
wall, or structural member
setting for LOW
CALIBRATION POINT
(2.3.5.1.) (Page 123) not cor-
rect
setting for SENSOR OFFSET
(2.3.5.3.) (Page 124) not cor-
rect
power error
echo confidence weak
material filling
FILL RATE/MIN (2.3.6.2.)
(Page 126) setting incorrect
Action
check specifications
check LOW CALIBRATION POINT (2.3.5.1.) (Page 123).
increase CONFIDENCE (2.4.7.1.) (Page 132).
Use the air purge feature to clean the antenna
re-locate SITRANS LR560.
check to ensure nozzle is vertical
ensure end of antenna protrudes from end of nozzle
review MAXIMUM MEASURED VALUE (3.5.2.)
(Page 144)
ensure Auto False Echo Suppression Range is set correct-
ly
check temperature in MAXIMUM VALUE (3.4.2.)
(Page 144).
relocate
re-locate SITRANS LR560
check nozzle for internal burrs or welds
rotate device 90°
use AUTO ECHO SUPPRESSION (2.4.8.1.) (Page 132) if
necessary.
check distance from sensor reference point to LOW
CALIBRATION POINT (2.3.5.1.) (Page 123)
check SENSOR OFFSET (2.3.5.3.) (Page 124)
check nameplate rating against voltage supply
check power wiring or source
refer to CONFIDENCE (2.4.7.1.) (Page 132).
use AUTO ECHO SUPPRESSION (2.4.8.1.) (Page 132)
and AUTO SUPPRESSION RANGE (2.4.8.2.) (Page 134)
use foam deflector or stillpipe
Re-locate SITRANS LR560.
increase measurement response if possible
Diagnosing and troubleshooting
10.3 Operation troubleshooting
169

Advertisement

Table of Contents
loading

Table of Contents