10.3
Operation troubleshooting
Operating symptoms, probable causes, and resolutions.
Symptom
Display shows
Display shows
Display shows
Display shows
Reading does not
change, but the level
does
Measurement is con-
sistently off by a con-
stant amount
Screen blank
Reading erratic
Reading response
slow
LR560 (FOUNDATION FIELDBUS)
Operating Instructions, 06/2018, A5E34648692-AE
Cause
level or target is out of range
material build-up on antenna
location or aiming:
poor installation
•
flange not level
•
Auto False Echo Suppression
•
may be incorrectly applied
antenna malfunction:
temperature too high
•
physical damage
•
SITRANS LR560 processing
wrong echo, for example, vessel
wall, or structural member
setting for LOW
•
CALIBRATION POINT
(2.3.5.1.) (Page 123) not cor-
rect
setting for SENSOR OFFSET
•
(2.3.5.3.) (Page 124) not cor-
rect
power error
echo confidence weak
material filling
FILL RATE/MIN (2.3.6.2.)
(Page 126) setting incorrect
Action
check specifications
•
check LOW CALIBRATION POINT (2.3.5.1.) (Page 123).
•
increase CONFIDENCE (2.4.7.1.) (Page 132).
•
Use the air purge feature to clean the antenna
•
re-locate SITRANS LR560.
•
check to ensure nozzle is vertical
•
ensure end of antenna protrudes from end of nozzle
•
review MAXIMUM MEASURED VALUE (3.5.2.)
•
(Page 144)
ensure Auto False Echo Suppression Range is set correct-
•
ly
check temperature in MAXIMUM VALUE (3.4.2.)
•
(Page 144).
relocate
•
re-locate SITRANS LR560
•
check nozzle for internal burrs or welds
•
rotate device 90°
•
use AUTO ECHO SUPPRESSION (2.4.8.1.) (Page 132) if
•
necessary.
check distance from sensor reference point to LOW
•
CALIBRATION POINT (2.3.5.1.) (Page 123)
check SENSOR OFFSET (2.3.5.3.) (Page 124)
•
check nameplate rating against voltage supply
•
check power wiring or source
•
refer to CONFIDENCE (2.4.7.1.) (Page 132).
•
use AUTO ECHO SUPPRESSION (2.4.8.1.) (Page 132)
•
and AUTO SUPPRESSION RANGE (2.4.8.2.) (Page 134)
use foam deflector or stillpipe
•
Re-locate SITRANS LR560.
•
increase measurement response if possible
•
Diagnosing and troubleshooting
10.3 Operation troubleshooting