Sensor reference point
Distance (SV2)
Low calibration point (process empty level)
8.2.5.4

INPUT SCALING (2.5.4)

Input scaling should match the XD_scale from the Level Transducer Block. See the manual
Foundation Fieldbus for Level instruments (7ML19985MP01) for more detail.
LOWER VALUE (2.5.4.1.)
Factory setting:
Setting range:
Purpose:
UPPER VALUE (2.5.4.2.)
Factory setting:
Setting range:
Purpose:
LR560 (FOUNDATION FIELDBUS)
Operating Instructions, 06/2018, A5E34648692-AE
High calibration point (process full level)
Level (SV1)
0%
Range: -999999 to 999999
Defines the operational lower range value of the input value (Process
Value Scale) in PV (volume/level) Units. Process Value Scale normal-
izes the input value to a customer-defined range.
100%
Range: -999999 to 999999
Defines the operational upper range value of the input value (Process
Value Scale) in PV (volume/level) Units. Process Value Scale normal-
izes the input value to a customer-defined range.
Parameter Reference
8.2 SETUP (2.)
137