H3: Analog Inputs - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Setting Value
Function
1B2
!BAS Interlock
1B8
!Pump Fault
1B9
!Transducer Loss
1BA
!PI Auxiliary Control
Active
1BB
!Differential Feedback
Exceeded
1BC
!Sleep Active
1BD
!Start Delay
1BE
!Pre-Charge
1C0
!HAND Mode
1C1
!AUTO Mode
1C2
!OFF Mode
1C3
!Main Feedback Lost
1C4
!Backup Feedback Lost

H3: Analog Inputs

No.
Name
(Hex.)
H3-01
Terminal A1 Signal Level
Select
(0410)
H3-02
Terminal A1 Function
Selection
(0434)
H3-03
Terminal A1 Gain Setting
(0411)
RUN
H3-04
Terminal A1 Bias Setting
(0412)
RUN
H3-09
Terminal A2 Signal Level
Select
(0417)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the Run command is active or the drive is outputting the voltage. The drive will use this
as an actuation signal for an external damper.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when one of these faults is active: LFB [Low Feedback Sensed], HFB [High Feedback
Sensed], NMS [Setpoint Not Met], or EFx [External Fault (Terminal Sx)].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the current into the analog input associated with PID feedback is more than 21 mA or
less than 3 mA, or an FDBKL [WIRE Break] Fault or an FDBKL [Feedback Loss Wire Break] Alarm is active.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the PI Auxiliary Controller has an effect on the output speed.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the difference between the PID Feedback and the value from the terminal set for H3-xx
= 2D [Differential Feedback] is more than Y4-18 [Differential Level] for the time set in Y4-19 [Differential Lvl
Detection Time].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the Sleep function is active and the drive is not operating.
Note:
The terminal will not deactivate for Sleep Boost function.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the Feedback is more than the start level or the Feedback is less than the Inverse PID
and the start timer is timing.
Note:
You must set Y1-04 [Sleep Wake-up Level] ≠ 0 and Y1-05 [Sleep Wake-up Level Delay Time] ≠ 0 to use this
function.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive is in Pre-Charge Mode.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is in HAND Mode operation.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is in AUTO Mode operation.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is in OFF Mode operation.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive loses the main PID feedback.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive loses the backup PID feedback.
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
OLV/PM
OLV/PM EZOLV
Sets the function for MFAI terminal A1.
V/f
OLV/PM
OLV/PM EZOLV
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
OLV/PM EZOLV
OLV/PM
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
OLV/PM EZOLV
OLV/PM
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
1.10 H: Terminal Functions
Description
Ref.
324
324
324
324
324
324
324
324
324
324
324
324
324
Default
Ref.
(Range)
0
326
(0 - 3)
0
326
(0 - 31)
100.0%
326
(-999.9 - +999.9%)
0.0%
327
(-999.9 - +999.9%)
2
327
(0 - 3)
69
1