Setting Value
Function
1B2
!BAS Interlock
1B8
!Pump Fault
1B9
!Transducer Loss
1BA
!PI Auxiliary Control
Active
1BB
!Differential Feedback
Exceeded
1BC
!Sleep Active
1BD
!Start Delay
1BE
!Pre-Charge
1C0
!HAND Mode
1C1
!AUTO Mode
1C2
!OFF Mode
1C3
!Main Feedback Lost
1C4
!Backup Feedback Lost
◆
H3: Analog Inputs
No.
Name
(Hex.)
H3-01
Terminal A1 Signal Level
Select
(0410)
H3-02
Terminal A1 Function
Selection
(0434)
H3-03
Terminal A1 Gain Setting
(0411)
RUN
H3-04
Terminal A1 Bias Setting
(0412)
RUN
H3-09
Terminal A2 Signal Level
Select
(0417)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the Run command is active or the drive is outputting the voltage. The drive will use this
as an actuation signal for an external damper.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when one of these faults is active: LFB [Low Feedback Sensed], HFB [High Feedback
Sensed], NMS [Setpoint Not Met], or EFx [External Fault (Terminal Sx)].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the current into the analog input associated with PID feedback is more than 21 mA or
less than 3 mA, or an FDBKL [WIRE Break] Fault or an FDBKL [Feedback Loss Wire Break] Alarm is active.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the PI Auxiliary Controller has an effect on the output speed.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the difference between the PID Feedback and the value from the terminal set for H3-xx
= 2D [Differential Feedback] is more than Y4-18 [Differential Level] for the time set in Y4-19 [Differential Lvl
Detection Time].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the Sleep function is active and the drive is not operating.
Note:
The terminal will not deactivate for Sleep Boost function.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the Feedback is more than the start level or the Feedback is less than the Inverse PID
and the start timer is timing.
Note:
You must set Y1-04 [Sleep Wake-up Level] ≠ 0 and Y1-05 [Sleep Wake-up Level Delay Time] ≠ 0 to use this
function.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive is in Pre-Charge Mode.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is in HAND Mode operation.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is in AUTO Mode operation.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is in OFF Mode operation.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive loses the main PID feedback.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive loses the backup PID feedback.
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
OLV/PM
OLV/PM EZOLV
Sets the function for MFAI terminal A1.
V/f
OLV/PM
OLV/PM EZOLV
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
OLV/PM EZOLV
OLV/PM
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
OLV/PM EZOLV
OLV/PM
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
1.10 H: Terminal Functions
Description
Ref.
324
324
324
324
324
324
324
324
324
324
324
324
324
Default
Ref.
(Range)
0
326
(0 - 3)
0
326
(0 - 31)
100.0%
326
(-999.9 - +999.9%)
0.0%
327
(-999.9 - +999.9%)
2
327
(0 - 3)
69
1