[AL. 512_Memory error 1 (RAM) (safety sub-function)]

• The internal part of the servo amplifier (RAM) has malfunctioned.
[AL. 512.2_RAM diagnosis error A2 (safety sub-function)]
Cause
1.
An internal part of the servo amplifier has
malfunctioned.
2.
There is a problem with the surrounding
environment.
[AL. 512.3_RAM diagnosis error A3 (safety sub-function)]
Page 133 [AL. 512.2_RAM diagnosis error A2 (safety sub-function)]
[AL. 512.A_RAM diagnosis error B2 (safety sub-function)]
Page 133 [AL. 512.2_RAM diagnosis error A2 (safety sub-function)]
[AL. 512.B_RAM diagnosis error B3 (safety sub-function)]
Page 133 [AL. 512.2_RAM diagnosis error A2 (safety sub-function)]
Check/action method
Noise from the power supply may have caused the failure. Disconnect all
cables except for those for the control circuit power supply, then check the
repeatability. If the failure continues, the servo amplifier may have
malfunctioned. Replace the servo amplifier.
Check the power supply for noise. If there is noise, take countermeasures to
reduce the noise.
Refer to "Noise reduction techniques" in the following manual.
MR-J5 User's Manual (Hardware)
1 SERVO AMPLIFIER TROUBLESHOOTING
1.3 Handling methods for alarms/warnings