[AL. 0E5_ABS time-out warning]

• When transferring the absolute position data, it took more than 5 s for the programmable controllers to respond.
• During absolute position erased data transfer, ABSM (ABS transfer mode) turned off.
• SON (Servo-on), RES (Reset), EM2 (Forced stop 2), or EM1 (Forced stop 1) turned off during absolute position erased
data transfer.
[AL. 0E5.1_Time-out during ABS data transfer]
Cause
1.
The wiring of input/output signals is incorrect.
2.
The sequence program is incorrect.
[AL. 0E5.2_ABSM off during ABS data transfer]
Page 107 [AL. 0E5.1_Time-out during ABS data transfer]
[AL. 0E5.3_SON off during ABS data transfer]
Page 107 [AL. 0E5.1_Time-out during ABS data transfer]
Check/action method
Check for disconnection or loose connection in the I/O signal wire.
Modify the sequence program.
1 SERVO AMPLIFIER TROUBLESHOOTING
1.3 Handling methods for alarms/warnings
1
Model
[A]
107