Station Data; Integer Data (16-Bit Integer) - Siemens Moore 353 User Manual

Process automation controller
Table of Contents

Advertisement

UM353-1

7.2 STATION DATA

A station contains some data that pertains to the entire station and some to individual loops. Station data, available
over the network, is part of the station function block (STATN) configuration and is mapped to fixed locations in
Modbus registers or coils and fixed channel/parameters when the optional LIL board is installed. Loop data
(detailed in the next section) can be associated with a Controller "Control Loop" or a Sequencer "Sequencer Loop"
as defined by the selection of the operator display: ODC "Operator Display for Controller" or ODS "Operator
Display for Sequencer".
Much of the analog data is available is two formats. The first is 16-bit values, scaled consistent with previous LIL
products, enabling integration into existing LIL systems. This data type also provides Modbus masters, unable to
handle 32-bit floating point, a method for obtaining data from the station.
The second is the standard 32-bit IEEE floating point format consistent with the actual data in the station. This data
type is contained in two consecutive registers or parameters.
When using Modbus, the LSW is first and the MSW second.
When using LIL, the first parameter contains the MSW and the second parameter the LSW.
Boolean values are packed into 16-bit words for LIL use and are available in coils when using Modbus.
String data, formatted as 2 ASCII characters per word with the left-most character in the most significant byte,
containing tag, units, and message information is available with Modbus and LIL.
Most Station data is 'Read Only' except for:
SE (Station Error) parameter that allows a write of $0000 to reset the current error as an acknowledgment
SSW (Station Status Word) parameter which allows writes to certain bits (coils)
MLTP (Modbus Loop Trend Pointer, included in version 1.30 firmware) parameter
AASEL (Active Acknowledged Station Error Log, included in version 1.30 firmware) parameter
other items as noted below

7.2.1 Integer Data (16-bit Integer)

Code
R/W
Description
GDS
R
Global Data Size (LIL)
ST
R
Station Type
SSW
R/W
Station Status Word
SE
R/W
Station Error
NCL
R
No. of Control Loops (# of ODC)
NSL
R
No. of Seq. Loops (# of ODS)
RAM
R
RAM Size (size in K bytes)
CBT
R
Controller Board Type
CBSR
R
Controller Board Software Rev. #
EBT
R
Expander I/O Board Type
EBSR
R
Exp. I/O Board Software Rev. #
RBT
R
Remote I/O Board Type (A-1)
RBSR
R
Remote I/O (A-1) Software Rev. #
NBT
R
Network Board Type (B-1)
NBSR
R
Network (B-1) Software Rev. #
OAT
R
Option Board A Type (A-2)
OASR
R
Option A (A-2) Software Rev. #
OBT
R
Option Board B Type (B-2)
OBSR
R
Option B (B-2) Rev #
OFT
R
Operator Faceplate Type
DRN
R
Model 353 Database Rev. No.
CWT
R
Computer Watchdog Timer (sec)
March 2003
Range
Register (MB)
7-256 ($0007-$0100)
n/a
6 ($0006)
40001
(see Station Status Word)
(see coils)
0-32767($00000-$7FFF)
40002
0-255($0000-$00FF)
40003
0-255($0000-$00FF)
40004
0-65535($0000-$FFFF)
40005
(see below)
40006
(see below)
40007
(see below)
40008
(see below)
40009
(see below)
40010
(see below)
40011
(see below)
40012
(see below)
40013
(see below)
40014
(see below)
40015
(see below)
40016
(see below)
40017
(see below)
40018
0-32767($0000-$7FFF)
40019
0-1000 ($0000-$03F8)
40020
Data Mapping
C/P (LIL)
1/1
2/1
3/1
4/1
5/1
6/1
1/2
1/3
1/4
1/5
1/6
1/7
1/8
1/9
1/10
1/11
1/12
1/13
1/14
1/15
2/8
3/2
7-3