3.2.73 PB1SW - PB1 Switch

PB1SW is one of three general purpose switches available
in each loop. It can be utilized for switching Boolean
signals in such applications as: toggling Console/Local
operation of the ODC or ODS function blocks, Start/Stop,
controlling the position of a TSW (Transfer Switch)
function block for switching analog signals, or other
operator initiated actions.
PB1SW can be configured for momentary or sustained
operation. As momentary, the switch will transfer to the
NO position when the button is pressed and will return
when released. Momentary action is used in toggle
applications such as changing the function of the ODC or
ODS function blocks. In the sustained mode, the switch
will alternate positions each time the button is pressed. An
unconfigured NC input defaults to 0 and an unconfigured
NO input to 1. With firmware 1.30 and higher, the button
can be remotely activated through a command over
Modbus or LIL.
This block operates with an operator faceplate that includes green and red LEDs that are turned on using input MD.
A HI (1) input will turn on the Green LED and a LO the Red LED. The default connection will be the PS output of
the block but should be changed as required to display the correct status. The message parameters do not apply to
the current product.
PB1 Switch
Operator Display Interface
BOD LEDS
MD HI ST
G
PB1
MD LO ST
R
NC
NO
Momentary Action
Sustained Action
X03126S0
BLOCK DIAGRAM
3-76
MSG
MD HI AC
*****
*****
MD
MD LO AC
MD Input
*****
*****
PS
PB Switch
Output
BOD - Basic Operator Display
MD - Message Display
PB1 SWITCH
PB1SW
ESN = 000
NC Input
NC
PB1 Switch
NO Input
NO
Message Display
MD
A
C
T
I
O N
Switch ACTION
P
U
L
A
S T
Power Up LAST
S
M
D
H
I
T
MD HI STatus message
M D
L
O
S T
MD LO STatus message
M D
H
A C
I
MD HI ACtion message
M D
O
A C
L
MD LO ACtion message
I
N P U T
N C
INPUT NO
...........
(H)
I
N P U T
N O
INPUT NC
...........
(H)
N P U T
I
M D
INPUT MD
...........
(H)
E
S
N
Exec. Seq. No.
POWER UP - When the switch is configured for
momentary action, it will always power up in the NC
position. For sustained action, with the POWER UP
parameter set to YES, the switch will power up in the
last position during a hot or warm start, and during a
cold start will power up in the NC position. When
the POWER UP parameter is set to NO, the switch
will power up in the last position during a hot start.
During a warm or cold start, it will power up in the
NC position.
UM353-1
PB/Switch Output
PS
................... MOM/SUS
(MOM)
(S)
...................... NO/YES
(YES)
(S)
.. 5 ASCII Char (GREEN)
(S)
. 5 ASCII Char
(RED)
(S)
... 5 ASCII Char
(RED)
(S)
. 5 ASCII Char (GREEN)
(S)
loop tag.block tag.output
(null)
loop tag.block tag.output
(null)
loop tag.block tag.output
(null)
..................... 001 to 250
(H)
March 2003