Maintenance
Display Format:
ERR: x x x
Error Indication
Error Type:
1
Fatal
The station cannot operate until the source of the error has been corrected.
2
Non-Fatal
Correct error from faceplate or communication port.
Board Type:
0
MPU Controller
1
I/O Expander
2
LIL Network
3
LonWorks Remote I/O
8
RCB or RTC/CB
9
Ethernet Network
Test Type:
0
RAM Test
- MPU Controller board - Fatal error, replace board. Press ENTER to repeat test.
- Option Board - Station operation suspended. Pressing ENTER will cause all references
to blocks relating to the option board to be removed from the configuration and removal
of the board from the availability list.
1
Flash CRC Test
- MPU Controller board - Station operation suspended until new code is downloaded.
Press ENTER to repeat test.
- Option Board - Station operation suspended until new code is downloaded. Pressing
ENTER will cause all references to blocks relating to the option board to be removed
from the configuration and removal of the board from the availability list.
2
Constant Data
Station operation suspended until new constant data is downloaded. Press ENTER to
CRC Test
load board specific default constant data.
3
Calibration Data
Station operation suspended until ENTER is pressed to load default calibration data.
CRC Test
4
Software
Station operation suspended until new code is downloaded. Pressing ENTER will cause
Compatibility
all references to blocks relating to the option board to be removed from the configuration
Test
and removal of the board from the availability list.
5
Database
Station operation suspended until new constant data is downloaded. Press ENTER to, if
Compatibility
possible, convert the database or load board specific default constant data.
Test
6
Board Not
Station operation suspended. Install the missing board or press ENTER to remove from
Present Error
the configuration all references to the missing board.
7
Hardware
Fatal error. Repair or replace as necessary. Press ENTER to repeat test.
Communication
(QSPI) Test
8
Board
Remove the board causing the error and install a compatible board.
Compatibility
Ethernet Board - Upgrade Ethernet firmware to V3.0 or higher.
Test
Real Time Clock/Configuration Backup board and Removable Configuration Board (RCB) off-line error codes are
listed in Table 11.1. RTC/CB and RCB on-line status codes are located in Table 11.2 and listed as "RCB" errors.
11-8
Test Type
Board Type
Error Type
UM353-1
March 2003