UM353-1

3.2.14 AOE_ - Analog Output- Ethernet (V2.4)

AOE_ function blocks are available when the optional
Ethernet communication board is installed. Up to 32 AOE
blocks are available and are assigned in sequence with each
use, station wide.
The range pointer parameter (Input R) enables the block to
pass the range scaling to AIE function blocks in other
Moore and Procidia controllers connected over the Ethernet
network.

3.2.15 AOL_ - Analog Output - LIL

AOL_ function blocks are available when the optional LIL
communication board is installed. They enable the station
to provide a LIL global output, received as an
interconnection from another function block. AOL block
numbers are assigned in sequence with each use, station
wide. The configuration requires the entry of a LIL
Channel number to which the data is to be assigned. The
range pointer parameter (input R) enables the block to
scale the LIL global output (GO), in the standard $80-$F80
range, for the range of input S. If the pointer is not
configured the value will be scaled as 0.00 to 100.00.
1
2
3
n
GO
MINSCALE
March 2003
L
I
I N P U T
4
5
6
7
MAXSCALE
ANALOG OUTPUT - ETHERNET
AOE_
Range
R
ANALOG OUTPUT
ETHERNET
Input S
S
R G
P T R
RanGe PoinTeR
.............. loop tag.block tag
(S)
I N P U T
S
INPUT S
............... loop tag.block tag.output
(H)
ANALOG OUTPUT - LIL
AOL_
Range
R
ANALOG OUTPUT - LIL
Input S
S
L
C
H
A
N
LIL CHANnel
.................................
(H)
R G
P T R
RanGe PoinTeR
.............. loop tag.block tag
(S)
S
............... loop tag.block tag.output
INPUT S
(H)
8
9
10`
ENG UNITS
Input S
Function Blocks
(null)
(null)
(Rev. 2)
LIL
GLOBAL
DATA
006 to 255 (null)
(null)
(null)
11
256
105
3-25