Function Blocks

3.2.32 DIE_ - Digital Input - Ethernet (V3.0)

DIE_ function blocks are available when the
optional Ethernet communication board
installed in the controller. It enables the controller
to read digital data from other stations over the
Ethernet network.
Up to 32 DIE_ blocks are available. Blocks are
assigned in sequence, controller wide, with each
use. Digital data is On/Off data packed into a 16-bit
word. This data is fanned out to block outputs D0 –
DF.
The IP ADRES parameter is used to configure the
IP address of the source device. The MB ADRES
parameter allows a Modbus address to be
configured. When connecting to other Siemens
MOORE controllers, the Modbus address is set to 1.
In some cases, other devices may use a different
address or when going through a Modbus TCP/IP gateway a Modbus network may have multiple devices, each
having a unique address.
The MB REG parameter identifies the location of the digital data in the source device. The REG TYP parameter
enables reading of Holding Registers (Modbus Function Code 03) or Input Registers (Modbus Function Code 04).
Both are treated the same in most Modbus devices but the Input type is the most common usage. The use of DOE
blocks in other Siemens MOORE controllers as the input source is defined by using the Modbus Registers from the
table below. The UD RATE parameter configures the rate at which the block will request data. The P2P setting
will update the data at the rate set by the P2P RATE parameter in the ETHERNET block. The Ct setting will update
the data at the cycle time of the controller.
Output QS indicates the quality of the received data and will go high (1) when the data is bad. This is normally
associated with failure to receive data due to a communication failure or a misconfiguration of the source.
FB
MB
Number
Register
DOE01
31025
DOE02
31026
DOE03
31027
DOE04
31028
DOE05
31029
DOE06
31030
DOE07
31031
DOE08
31032
10
Requires Ethernet communications board firmware version 2.0 or later
3-40
10
is
FB
MB
Number
Register
Number
DOE09
31033
DOE17
DOE10
31034
DOE18
DOE11
31035
DOE19
DOE12
31036
DOE20
DOE13
31037
DOE21
DOE14
31038
DOE22
DOE15
31039
DOE23
DOE16
31040
DOE24
DIGITAL INPUTS 16 CHAN - ETHERNET
DIE_
DIGITAL INPUTS
16-CHAN ETHERNET
I
P
A
D
R E S
IP A DdRES s
M
B
A D R
E
S
MB A DdRESs
M B
R
E
G
MB REG ister
U
D
R
A
T E
UpDate RATE
R E G
T
Y
P
E
REG ister TYPE
FB
MB
FB
Register
Number
31041
DOE25
31042
DOE26
31043
DOE27
31044
DOE28
31045
DOE29
31046
DOE30
31047
DOE31
31048
DOE32
UM353-1
D0
Output D0
DF
Output DF
QS
Output QS
....
nnn.nnn.nnn.nn n
(H)
(192.168.0.0)
............... 0 - 255
(1)
(H)
....... 0000 - 65535
(null)
(H)
............. P2P/Ct
(P2P)
(H)
. InPut /Hold ing
(InPut)
(H)
MB
Register
31049
31050
31051
31052
31053
31054
31055
31056
March 2003