UM353-1
Controller Terminals
_
26 Vdc
5
Digital Output
8
Common
9
Common Ground Bus
Earth
Ground
A. Current Output, Isolated
Controller Terminals
_
26 Vdc
5
8
Digital Output
9
Common
Common Ground Bus
Earth
Ground
C. Current Output, Isolated
Figure 8-15 Digital Output DOUT1, Resistive and Inductive Loads
March 2003
Resistive Load
(+)
(-)
Inductive Load with
Suppression Diode,
See Note
+
24 Vdc
_
Notes:
1. Inductive load must be shunted with a transient
suppression diode (1N4005 or equiv.) to prevent
damage to station output circuit.
2. See Table 8.1 for DOUT2 terminal numbers.
Controller Terminals
_
26 Vdc
5
10K Typical
8
Digital Output
9
Common
Common Ground Bus
Earth
Ground
B. Voltage Output, Non-Isolated
Installation
Resistive Load
(+)
(-)
8-17