UM353-1

3.1 STATION FUNCTION BLOCKS

Station function blocks include factory configured options (FCOs), security, and station parameters. Each is
described in the following subsections.

3.1.1 FCO LIB - Factory Configuration Library

The FCO LIB function block provides a selection of pre-
configured applications. An FCO can be selected from
the library and "STORED". This loads a complete
controller configuration, as defined by the FCO
documentation, and erases any previously stored
configuration. Station parameters and Calibration are
retained when a new FCO is loaded. This enables a user
to quickly configure the controller with an FCO without
having to re-calibrate or re-enter the Station parameter
values.
Upon stepping down to the FCO parameter, the last FCO
that was loaded in the controller will be displayed.
Turning the pulser knob will then display other FCOs
that are available in the FCO library.
The configuration installed at the factory will be either FCO 101 or a custom configuration that was ordered and
defined by the user. FCO 101 is a basic single loop PID controller.
An FCO can be loaded at any time in the field and used as is or modified (edited) to meet individual requirements.
The FCO library file is not modified when the FCO selected for controller configuration is edited.

3.1.2 SECUR - Security

The SECUR function block enables a user to lock out
portions or all of the faceplate configuration functions.
Five levels of security are available; see Table 3.1.
Each level is factory set to 000000 (no security), and
can be changed by the user in the field to any number
up to 999999.
A security combination should be assigned to each
security level (1-highest, 5-lowest). A level that
remains at the default 000000 combination will have no
security for the involved function(s) regardless of the
security assigned to the other levels. For example,
assume that level 1 is assigned a security combination
but level 4 remains at 000000. If a controller
calibration is performed, the station will not prompt the
user for the security combination and anyone will be
able to store new calibration values.
If security is desired, it is recommended that all 5 levels of security be set with either the same value or different
values when different individuals are granted access to only certain functions.
March 2003
FCO LIBRARY
FCO LIB
FCO LIBRARY
F C
O
Factory Configured Option
SECURITY
SECUR
SECURITY
L
E V
1
C O
M
LEVel 1 COMbination
C O
L
E V
2
M
LEVel 2 COMbination
L
E V
3
C O
M
LEVel 3 COMbination
L
E V
4
C O
M
LEVel 4 COMbination
L
E V
5
C O
M
LEVel 5 COMbination
Function Blocks
....... 0 - 999999 (00)
(H)
.... 000000-999999 (000000)
(S)
.... 000000-999999 (000000)
(S)
.... 000000-999999 (000000)
(S)
.... 000000-999999 (000000)
(S)
.... 000000-999999 (000000)
(S)
3-3