Siemens Moore 353 User Manual page 263

Process automation controller
Table of Contents

Advertisement

UM353-1
TABLE 11.1 RTC/CB and RCB Boards, Off-Line Error Codes
ERROR
DESCRIPTION
CODE
ERR280
Board failed NVRAM test
ERR282
Configuration on Board failed checksum
test and is corrupted.
ERR284
Configuration on Board is not compatible
with MPU Controller board firmware
level. This will occur only when the Board
comes from a controller with a different
MPU Controller board firmware level
than the current controller and some
functions in the configuration database
cannot be supported by the current
firmware.
ERR285
Configuration on Board is not compatible
with MPU Controller board database. This
will occur only when the Board comes
from a controller with a higher MPU
Controller firmware level than the current
controller. Controller firmware can
convert a database created with a lower
firmware revision level but not a higher
level.
ERR286
The controller powered down with a Board
installed but could not identify it on power
up. The board may have been removed or
the board ID may be corrupted.
ERR288
The LonWorks circuit board currently
installed is not compatible with the
LonWorks configuration contained on the
Board.
ON-LINE ERROR CODES AND STATUS CODES
These codes can be produced while the controller is running function block and may be actively controlling a
process. Depending on the message and its priority level, user intervention may be required or the message may
simply be informational in nature. LIL parameter "SE" located at channel 4, parameter 1 (Modbus register $40002)
will reflect unacknowledged error or status messages present in the controller. Messages are displayed according to
priority until all active messages have been acknowledged. If no link code has been assigned to the active message,
the "SE" code will remain at its last value.
Table 11.2 lists on-line error and status codes. For most error codes, replace the involved circuit board to repair the
controller. For most status codes, acknowledge or otherwise respond to the situation.
March 2003
CORRECTIVE ACTION
1) Power down and replace Board.
2) Press ENTER to ACK error. Controller will go on-
line using configuration in MPU memory.
1) Power down and install a Board containing a valid
configuration.
2) Press ENTER to ACK error. Controller will go on-
line using configuration in MPU memory that will
also be loaded into the Board.
1) Install MPU firmware compatible with the Board
configuration
2) Press ENTER to ACK error. Controller will go on-
line using configuration in MPU memory. The
configuration will remain intact until a parameter is
STOREd, at which time the MPU configuration
will be transferred to the Board.
1) Install MPU firmware compatible with the Board
configuration
2) Press ENTER to ACK error. Controller will go on-
line using configuration in MPU memory. The
configuration will remain intact until a parameter is
STOREd, at which time the MPU configuration
will be transferred to the Board.
1) Install a Board or new Board.
2) Press ENTER to ACK error. Controller will go on-
line using configuration in MPU memory.
1) Power down and install the LonWorks board from
the same controller that the Board came from.
2) Press ENTER to ACK error. Controller will go on-
line. Any existing LonWorks network data will be
used if it is valid, otherwise, it will be set to default
values. In either case, the LonWorks network
manager will be required to re-establish the
network bindings.
Maintenance
11-9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents