Extended Control Loop Status Word (L#ECLS) - channel n+4/parameter 10
BIT
Description
0
Not Ack'd STANDBY
1
Not Ack'd Override
2
Not Ack'd Emergency Manual
3
Not Ack'd HI Setpoint Limit
4
Not Ack'd LO Setpoint Limit
5
Not Ack'd User 1 Status
6
Not Ack'd User 2 Status
7
Not Ack'd Autotune W1 Warning
8
Not Ack'd Autotune W2 Warning
9
Not Ack'd Autotune W3 Warning
10
Not Ack'd Autotune E1 Warning
11
Not Ack'd Autotune E2 Warning
12
Not Ack'd Autotune E3 Warning
13
Transfer Autotune Parameters
14
PB1SW Input MD (*)
15
PB2SW Input MD (*)
* These bits indicate the status of the switch input MD. A write of a "1" will have the same effect as pressing and
releasing the button on the faceplate. If the action of the switch is sustained the switch will change position. If
the action is momentary, the switch will close for one scan cycle.
March 2003
Value
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Not Acknowledged
1-Transfer
1-High, 0-Low
1-High, 0-Low
Data Mapping
Block
Read/Write
Output
A/M
R/W
A/M
R/W
A/M
R/W
SPLIM
R/W
SPLIM
R/W
ODC
R/W
ODC
R/W
PID
R/W
PID
R/W
PID
R/W
PID
R/W
PID
R/W
PID
R/W
PID
W
PB1SW
R/W
PB2SW
R/W