Data Mapping
PCOM Function Block Status Word (L#PSW1) - channel z/parameter 1
BIT
Description
0
INIT_OK
1
DFAIL
2
RESET
3
START
4
RESTART
5
HOLD
6
PCOMP
7
ABORT
8
READY
9
RUN
10
HELD
11
DONE
12
ABORTED
13
spare
14
spare
15
spare
PCOM Function Block Status Word (L#PSW2) - channel z+1/parameter 1
BIT
Description
0
EMERG (EO)
1
EO Not Acknowledged
2
INTRLK (IK)
3
IK Not Acknowledged
4
FAILED (FD)
5
FD Not Acknowledged
6
spare
7
spare
8
spare
9
spare
10
spare
11
spare
12
spare
13
spare
14
PCOM Not Acknowledged
15
ACTIVE PCOM Event (EO,IK,FD)
z - LIL CHAN configured in the PCOM function block configuration.
7-32
Value
1-INIT_OK
1-DFAIL
1-RESET
1-START
1-RESTART
1-HOLD
1-PCOMP
1-ABORT
1-READY
1-RUN
1-HELD
1-DONE
1-ABORTED
Value
1-EO is Active
1-EO is not acknowledged
1-IK is Active
1-IK is not acknowledged
1-FD is Active
1-FD is not acknowledged
1-PCOM is not ack'd
1- PCOM event is active
Block
Read/Write
PCOM
R/W
PCOM
R/W
PCOM
W
PCOM
W
PCOM
W
PCOM
W
PCOM
W
PCOM
W
PCOM
R
PCOM
R
PCOM
R
PCOM
R
PCOM
R
PCOM
PCOM
PCOM
Block
Read/Write
PCOM
R
PCOM
R/W
PCOM
R
PCOM
R/W
PCOM
R
PCOM
R/W
PCOM
R
PCOM
R
PCOM
R
PCOM
R
PCOM
R
PCOM
R
PCOM
R
PCOM
R
PCOM
R/W
PCOM
R