Siemens SIMATIC ET 200SP Operating Instructions Manual page 36

Technology module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Commissioning
5.2 Automatic calibration
Requirements
Automatic calibration requires the following criteria:
● Correct mechanical installation of the scale without shunt forces
● Scale is empty (only mechanical installation (= dead load) present on the cells)
● Installed load cells are evenly loaded
Procedure
1. During the first commissioning, reset using the electronic weighing system with the
command "Load factory settings (11)" or "Load standard parameter (12)".
2. Select the "Service mode ON (1)" command.
3. Read DR10.
4. Specify the load cell parameters in DR10 (Page 78).
5. Write DR10.
6. Select the "Service mode OFF (2)" command.
7. Start the "Automatic calibration (82)" command.
Result
The characteristic curve of the scale is calculated using the specified load cell parameters from
DR10 and the currently applied dead load. The characteristic curve is active immediately.
The characteristic data from DR03 is overwritten with the command "Automatic calibration
(82)".
36
Technology module TM SIWAREX WP351 HF
Operating Instructions, 01/2020, A5E47521010-AA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tm siwarex wp351 hf

Table of Contents