Interrupts/diagnostic messages
9.4 Operating errors
Technology messages
2105 Set point too small
2106 Error fine weight
2107 Stop after tolerance error
2108 Emptying parameter not plausible 2108
2109 Inhibition time violation "Coarse"
2110 Inhibition time violation "Fine"
2111 Maximum weighing time exceeded 2111
2112 Logging not possible - no standstill 2112
2113 Maximum emptying time excee‐
ded
2114 Maximum corrective action of the
proportional controller exceeded
2115 Log error
2116 Set point too large
2117 Maximum corrective action of the
fine signal time controller exceeded
2118 Minimum fine weight reached
2119 Controller re-initialized
2120 Weight too small for totalizing
2121 Autom. Tare/Zeroing not possible
132
Error code
Description and remedy
2105
The currently specified set point is too small.
Remedy: Check the set point setting in DR20.
2106
Trailing weight (DR23) and single set point (DR20) are incompati‐
ble. Check the two entries.
2107
The weighing cycle was stopped due to a tolerance error according
to the parameter assignment in DR22.
The emptying parameter assignment set in DR25 stops the weigh‐
ing cycle.
1. Adjust the parameter assignment during the stopped cycle.
2. Conclude the weighing cycle with the "Continue weighing
(1141)" command.
2109
After expiration of the blocking time coarse signal (DR23), the
coarse shut-off point has already been exceeded. Remedy: De‐
crease the blocking time coarse signal in DR23.
2110
After expiration of the blocking time fine signal (DR23), the fine shut-
off point has already been exceeded. Remedy: Decrease the block‐
ing time fine signal in DR23.
The maximum weighing time specified in DR25 was exceeded.
The conditions required for automatic logging (e.g. stability) were
not present at the time of the log print. Remedy: Check the stability
criteria in DR03 and adapt them as necessary.
2113
The maximum emptying time configured in DR25 was exceeded
during emptying.
Remedy: Check the scale mechanics and any soiling. Adjust the
maximum emptying time in DR25.
2114
The corrective action of the proportional controller was greater than
the maximum corrective action configured in DR24.
2115
Error while reading a log in DR46.
2116
The set point specified in DR20 is greater than the residual quantity
on the scale (removal mode). Weighing can still be carried out using
the "Continue weighing" and subsequent "Rest weighing" com‐
mands!
2117
The maximum control access of the fine time controller was greater
than the maximum corrective action configured in DR24.
2118
Fine signal time controller cannot move the coarse flow shut-off
point any further because the set coarse trailing weight would oth‐
erwise be undershot.
2119
Due to two successive disabling time violations, the controller with
the start values from DR23 was re-initialized.
2120
The currently loaded / dosed material weighs less than the mini‐
mum weight and is not logged automatically.
● Log the material with the "Rest weighing (1125)" command.
Result: Loading is stopped and total T1 is logged.
2121
Weighing was canceled because automatic tare or zeroing was not
possible.
Check the zeroing limits and tare limits in DR03 and DR25.
Technology module TM SIWAREX WP351 HF
Operating Instructions, 01/2020, A5E47521010-AA