10. (Optional) In this mode, an Automated Power Schedule can be setup to save on battery life
or on cellular charges. Go to the Settings then Serial Mode Setup tab. Enter a Start (power-
on) Time, On Duration, and Repeat Cycle.
The modem automatically turns off at midnight. It turns on at the Start (power-on) Time for
the On Duration. It then turns on again every Repeat Cycle until midnight, at which point it
will turn off.
For example: With the following settings of Start (power-on) Time of 22:00, On Duration of
10 minutes, and Repeat Cycle of Every Hour the cellular module will turn on for ten minutes
only twice each day. It will turn on at 10:00 pm and 11:00 pm. It will not turn on at midnight
since it is powered off at the start of the next day.

6.4.4.2 Configure data logger (optional)

SendVariables()
LoggerNet. It has the following syntax: 
SendVariables
(ResultCode, ComPort, NeighborAddr, PakBusAddr, Security, TimeOut,
"TableName", "FieldName", Variable, Swath )
The ComPort needs to be set to ComRS232 or ComSDC8 depending on how you have the
module connected to the data logger. Set the TableName to "Public" and the FieldName
to "Callback". The remaining parameters in the instruction are ignored. The resulting instruction
will look similar to: 
SendVariables
Scratch, 1)
is used to initiate a data logger call-back attempt to a computer running
(SendResult, COMRS232, 0, 4094, 0000, 0,
"Public"
CELL200-Series 4G LTE Cellular Module
,
"Callback"
,
46