Chapter 5
6.
string consists of a list of ASCII characters, octal or hex bytes, or special
symbols. You must enclose the entire sequence of characters in quotation
marks. An octal byte consists of a backslash character followed by the octal
value. For example, octal 40 is represented by \040. A hex byte consists
of a backslash character and a character x followed by the hex value. For
example, hex 40 is represented by \x40. The two special symbols, \r for
a carriage return character and \n for a linefeed character, are a more
convenient method for inserting the carriage return and linefeed characters
into the string as shown in this example: "F3R5T1\r\n". Because the
carriage return can be represented equally well in hex, \xD and \r are
equivalent strings.
7.
Valid options for buffer are 0, 1, 2, and 3, which denote off, ascii,
full, and brief, respectively.

Set (Select Device or Board)

Use the set command to change which device you are communicating with.
dev1:
plotter:
This example assumes that you used ibconf to define the name plotter and
that you had already called ibfind plotter during an earlier ibic session.
The following example summarizes the use of ibfind and set in a typical
program.
© National Instruments Corp.
ibic—Interface Bus Interactive Control Utility
set plotter
5-19
NI-488.2M SRM for OS/2