Advertisement

5

Troubleshooting

5.1 Alarm Messages

Alarm messages are displayed on the LCD control panel. Press the "UP" and "DOWN" buttons to scroll through all alarm messages.
Table 5.1a Warning Message List
Warning Message
MAIN VOLT/FREQ NOK
MAIN SEQUENCE NOK
BYPASS VOLT/REQ NOK
BYPASS SEQUENCE NOK
BYPASS STATIC SWITCH OVER TEMPERATURE
BYPASS STATIC SWITCH FAULT
BYPASS STATIC SWITCH OVERLOAD
UPS INTERNAL COMM ABNORMAL
BAT TEST FAIL
BAT OVER CHARGE
BATTERY BAD
BYPASS FAN FAILURE
TRANSFORMER OVERHEAT
UPS OUTPUT VOLT NOK
UPS EXT PARALLEL COMM ABNORMAL
PARALLEL FAILURE
REDUNDANCY LOSS
MANUAL BYPASS ON
BAT LOW WARNING
BAT LOW SHUTDOWN
BAT REPLACE REQUIRED
INVERTER OVERLOAD WARNING
INVERTER OVERLOAD SHUTDOWN
INVERTER OVER CURRENT
EMERGENCY POWER OFF ACTIVED
OUTPUT BREAKER OFF
BYPASS LOAD OVER 104%
BAT CABINET OVER TEMPERATURE
EXT BAT BREAKER OFF
Condition
Main input voltage abnormal
( load<70%: 120V~276V, load>70%:173V~276V )
Main input Freq. abnormal ( 45Hz~65Hz )
Main input phase sequence abnormal
Bypass voltage over rating
( 220V/230V/240V ) +/-15%
Bypass Freq. over rating ( 50Hz/60Hz )+/-5Hz
Bypass phase sequence abnormal
Bypass STS temperature over 80 degree C
Bypass STS open/short
Bypass loading over 175%
1.CAN BUS loss
2.SCI loss
3.Power module internal communication loss
Battery Capacity too low
Battery voltage more than 296V
Battery Voltage under 190V
Bypass FanA/B/C fail
IN/OUT transformer overheat warning (HW detect signal)
UPS output voltage over rating
( 220V/230V/240V ) +/-10V
Parallel CAN BUS loss
PID confl ict or system KVA rating not the same
UPS lost redundancy
Manual bypass on
Battery voltage under 220V and above 200V
Battery voltage under 200V
Battery package out of date
Loading over 105%
Loading over 105%~125% 10min.
Loading over 125%~150% 1min.
Loading over 150% 1sec.
Output current over 80A/phase
E.P.O./ Remote E.P.O. ON
Output breaker not turn on
the load over 104% when UPS is on bypass
Battery cabinet over 35 degree C
If support external battery and the breaker ont turn on
98
Chapter Index
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
5.2.6
5.2.7
5.2.8
5.2.9
5.2.10
5.2.11
5.2.12
5.2.13
5.2.14
5.2.15
5.2.16
5.2.17

Hide quick links: