Su80K Model - Tripp Lite SU60KX Manual

3-phase ups hardware introduction and troubleshooting su series
Hide thumbs Also See for SU60KX:
Table of Contents

Advertisement

1
Basic Operation (continued)
1.1 Technical Specifi cations (continued)

SU80K Model:

Input
Input Voltage
Voltage Regulation
Harmonic Distortion
PFC (Full Load)
Frequency
Frequency Tolerance
Output
Output Voltage
Output Frequency
Total Harmonic (Linear Load)
Voltage Regulation
Frequency Regulation
Overload
Audible Warning
Battery Backup
UPS Abnormal
Display
LED
LCD
Interface
Standard
Optional
Others
Parallel Redundancy
EPO
SRAM Event Log
Parameter Configuration
Hot Standby Installation
Battery Temperature Compensation
Battery Cold-Start
Overall
Efficiency
Transfer Time
Temperature
Humidity (non-condensing)
Noise (1 m)
Dimensions (Power Module)
Weight (Power Module)
Model (Capacity) SU80K (80kVA/64kW)
120/208V AC, 3Ø, 4-wire + ground, wye
-25% ~ +20%
< 5% (Full Load)
> 0.99
50 / 60 Hz
45 ~ 65 Hz
120/208V AC, 3Ø, 4-wire + ground, wye
50 / 60 Hz
≤3%
Static
±1%
Dynamic
±7% (10% ~ 90% Linear Load)
Interior Oscillator
±0.05 Hz
Synchronized
±5%
≤125% : 10 minutes; ≤150% : 1 minute
Intermittent
Continuous
UPS Status: Normal • Bypass • Backup • Fault
Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage
UPS abnormal messages with intelligent self-diagnosis.
RS-232, Dry Contact
SNMPWEBCARD
Yes (1+1 for 2 UPS systems of the same type and capacity only.)
Standard (Local and Remote)
500 Records
Yes
Optional
Optional
Standard
Normal
92%
ECO
96%
0 ms
32° F ~ 104° F (0° C ~ 40° C)
90%
70 dBA
Width
520 mm
Depth
1026 mm
Height
1696 mm
655 kg
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Su20kxSu40kxSu80kxSu40kSu60kSu60ktv ... Show all

Table of Contents