Basic Operation (continued)
1.2 Features (continued)
Note: Individual models may vary from diagrams. Unit shown with front bezels removed.
H
Levelers:
The levelers provide long-term support for the UPS system.
I
Casters:
The casters are designed for small position adjustments within the final installation location only; they are not designed for moving
the UPS system over longer distances. The casters are not designed to provide long-term support for the UPS system after final installation.
Use the levelers to provide long-term support.
J
Accessory Slot:
Remove the cover panel to install a Tripp Lite SNMPWEBCARD accessory. The SNMPWEBCARD accessory provides an
Ethernet interface for the UPS system and enables remote monitoring and control via SNMP, Web browser or telnet. Call (773) 869-1234 for
more information about the SNMPWEBCARD accessory.
K
RS-232 Serial Communications Port:
shutdown during extended blackouts and monitoring of operating and power conditions.
L
Parallel Redundancy Port:
redundancy (1+1) configuration. (See sections 1.5 and 1.8 for more information.)
M
Input Dry Contact Interface:
external battery conditions.
N
Output Dry Contact Interface:
for more information.)
O
Internal Battery Circuit Breaker Switch (SU40K only):
Terminal Block Cover:
Remove the terminal block cover to access the UPS system's input, external battery cabinet, output and grounding
P
connection terminals. Wiring conduits pass through the circular knockouts in the terminal block cover. (See section 1.8 for more information,
including a detailed diagram of the terminal block.)
L
H
Fig 1.2.3d SU40K rear
This DB9 port connects the UPS system to compatible workstations or servers, enabling automatic
This DB9 port connects the UPS system to another UPS system of identical type and capacity for use in a parallel
This interface receives dry contact signals that allow the UPS system to receive commands and monitor
This interface allows the UPS system to send information via dry contact communications. (See section 3.3
Controls the input/output power of the UPS system's internal batteries.
J
M
K
N
O
P
I
H
10