Battery Start-Up Procedure (Single Ups) - Tripp Lite SU60KX Manual

3-phase ups hardware introduction and troubleshooting su series
Hide thumbs Also See for SU60KX:
Table of Contents

Advertisement

1
Basic Operation (continued)
1.6 Start-Up, Shutdown and Bypass (continued)
1.6.3 Standard Start-Up Procedure (Single UPS) (continued)
3
Switch on the output circuit breaker switch
circuit breaker switch
B
. After a brief initialization process, the
LCD screen will show "ON AUTO BYPASS", the "BYPASS"
LED will illuminate and UPS system output will be supplied by the
bypass (reserve) power source.
Switch on the main input circuit breaker switch
4
power source is normal, the UPS system is ready for start-up.
5
Press the ON button
for 3 seconds (until you hear a beep), then
A
release the button. The inverter will activate and synchronize with
the bypass source, then automatically switch from auto bypass
(reserve) mode to online (normal) mode. The "BYPASS" LED will
darken and the "NORMAL" LED will illuminate.

1.6.4 Battery Start-Up Procedure (Single UPS)

Note: The battery must be at least partially charged for this operation to succeed.
If there is an external battery cabinet connected, switch on the
1
circuit breaker
A
of the external battery cabinet.
2
Confirm that the manual bypass circuit breaker switch
3
Press the ON button
A
for 3 seconds (until you hear a beep), then
release the button. The inverter will activate and use stored DC
battery power to supply AC power to connected equipment. The
"BATTERY" LED will illuminate.
A
and bypass input
3
. If the AC input
A
4
5
1
is off.
A
2
3
19
A
B
Output
Manual
Bypass
Bypass
Input
Output
Manual
Bypass
Bypass
Input
A
A
Output
Manual
Bypass
Bypass
Input
Main
Input
A
Main
Input
A
Main
Input
A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Su20kxSu40kxSu80kxSu40kSu60kSu60ktv ... Show all

Table of Contents