Calibrating Eeprom Gain - Tripp Lite SU60KX Manual

3-phase ups hardware introduction and troubleshooting su series
Hide thumbs Also See for SU60KX:
Table of Contents

Advertisement

3
Communication (continued)
3.1 Setting EEPROM on the NH-M Board (continued)

3.1.2 Calibrating EEPROM Gain

WARNING: This procedure must be performed in bypass mode (see section 1.6).
Instructions for calibrating the EEPROM gain of the UPS parameters are as follows:
(For polling procedure, please refer to section 3.1.1)
a) Click the "Gain" tab (Figure 3.1.2a)
Fig 3.1.2a
b) Select the parameter you want to calibrate and click its gain icon
c) Key in the actual value to the "Actual Measured:" column of the dialogue box
d) Key in the LCD value to the "UPS Detected:" column of the dialogue box
e) Click the "Calculate" icon (the New Gain Value will auto-calculate)
f) Click the "OK" icon (the dialogue box will close)
g) After calibrating the gain, click "Update All" and wait for the procedure to complete itself