Start-Up, Shutdown And Bypass; Control Panel And Breaker Diagrams; Preliminary Checklist (Single Ups); Standard Start-Up Procedure (Single Ups) - Tripp Lite SU60KX Manual

3-phase ups hardware introduction and troubleshooting su series
Hide thumbs Also See for SU60KX:
Table of Contents

Advertisement

1
Basic Operation (continued)

1.6 Start-Up, Shutdown and Bypass

Warning: The UPS system's output voltage is set at 220/380V by default. If you require output voltage of 230/400V or 240/415V, you must
change the UPS system's output voltage by accessing the output setup menu described in Section 10-9 of the owner's manual. You must
place the UPS system in bypass mode before changing the output voltage. Do not connect your equipment to the UPS system's output until
you have set the proper parameters.

1.6.1 Control Panel and Breaker Diagrams

"NORMAL" LED
A
"BATTERY" LED
B
"BYPASS" LED
C
"FAULT" LED
D
LCD Status Screen
E
F
"ESC" (Escape) Button
Scroll Buttons (
and
G
Enter Button (
)
H
I
ON Button
OFF Button
J
"EPO" (Emergency Power Off) Button
K
Output Circuit Breaker Switch
L
M
Manual Bypass Circuit Breaker Switch
Bypass Input Circuit Breaker Switch
N
Main Input Circuit Breaker Switch
O

1.6.2 Preliminary Checklist (Single UPS)

• All circuit breaker switches should be off, including the breaker of the external battery cabinet (if present).
• Confi rm that no voltage potential exists between Neutral and Ground.
• Confi rm that the input power source matches the rating (voltage, frequency and phase) of the UPS system.
Note: After start-up, the UPS system will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS
system will provide AC power to the connected equipment load.

1.6.3 Standard Start-Up Procedure (Single UPS)

1
If there is an external battery cabinet connected, switch on the
circuit breaker
of the external battery cabinet.
A
Confirm that the manual bypass circuit breaker switch
2
)
is off.
A
A
B
C
D
1
L
Output
Manual
2
Bypass
Circuit Breaker Switches (UPS System Front Panel)
A
1
A
Output
Manual
Bypass
2
18
E
F
I
K
G
H
J
Control Panel
M
N
O
Bypass
Main
Input
Input
Bypass
Main
Input
Input

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Su20kxSu40kxSu80kxSu40kSu60kSu60ktv ... Show all

Table of Contents