2
Theory of Operation (continued)

2.17 Communication Circuit for Input Dry Contact and REPO

Located on NH-SYS-R board (Circuit for RS232, Output Dry Contact, Parallel Port, Connector to connect with each Power Module,
Circuit for 2 Slots)
Located on NH-SYS-M board (System MCU and Control Circuit)
(a) System MCU will detect input dry contact via DRY_1 (79) and DRY_2 (80)
(b) REPO (Remote Emergency Power Off) can be detected via R_EPO (86) by system MCU (high active).
(c) When REPO has activated, System MCU will shut down the output. After the REPO release, the unit will stay in bypass mode.