Troubleshooting (continued)
5.2 Troubleshooting Flow Charts (continued)
5.2.14 "PS OUTPUT VOLT NOK"
Check if any power
module output voltages
are out of range
Note (1): Wire #10 connects CNP9 on the NH-SYS-P board with CNFC20 on the NH-SYS-FC board (Figure 5.2.14b).
Note (2): To learn about EEPROM parameter setting and calibration, refer to section 3.2.
Note (3): For the location of the NH-SYS-P board and NH-SYS-M boards, turn to section 1.5. To replace the NHS-SYS-M board, remove the
EEPROM chip from the old NHS-SYS-M board and insert it into the new one.
Note (4): Check the output voltage of each power module one at a time. If normal, check the next power module.
Start
Is the output
N
wire connection
OK?
Y
Are the
Actual value
N
and LCD value
the same ?
Y
(4)
END
Fix the connection
Is the
Y
LCD value
zero?
N
Replace P board or M
(3)
board
Calibrate parameter on
(2)
EEPROM
Fig 5.2.14a
Fig 5.2.14b
110
END
Fix the connection
N
Is the
(1)
Wire #10
connection
OK?
Y