11 Troubleshooting

1. If a problem occurs, ensure the mains input voltage is present before contacting service personnel.
2. Have the following information ready before contacting service personnel:
• Unit information, including model, serial number, etc.
• An exact description of the problem. The more detailed description of the problem, the better.
3. If the UPS displays an error code, refer to the following table to diagnose and resolve the problem.
Error Code Definition
E01
DC Bus Pre-Charge Abnormal
E04
Inverter Out of Range
E05
Battery Weak or Dead
E06
Inverter Short
E07
EPO Active
E08
Bus Over Charge
E09
Bus Under Charge
E11
Over Temperature Fault
E12
Overload Fault
E13
Charger Fault
E14
Fan Fault
E18
EEPROM Warning
E19
Site Fail
E20
Bus Discharge Fail
Utility Low
E24
E28
Bypass Overload
E29
Charge Over
E32
Bus Unbalance
E33
Inverter Fail
E35
Overload Warning
E36
Over Temperature Warning
Sd Code
Definition
Sd
UPS Will Shutdown
Note: If all possible causes are eliminated but the alarm still appears, contact your local dealer or service personnel.
Solution
Contact service personnel
Contact service personnel
1. Connect the battery cables firmly
2. Contact service personnel
1. Check whether the output has a short-circuit issue
2. Contact service personnel
After emergency events are eliminated, follow the start-up procedures
to turn on the UPS.
Contact service personnel
Contact service personnel
1. Check whether the UPS's ventilation is normal
2. Decrease the loads
3. Check whether the fan is functioning normally
4. Clean the filters, if installed
Decrease the loads
Contact service personnel
1. Check if foreign matter is stuck in the fan; if yes, remove it
2. Contact service personnel
Contact service personnel
Ensure AC input L/N/G is correct
Contact service personnel
1. Check input voltage
2. Check battery connection
Decrease the loads
Contact service personnel
Contact service personnel
Contact service personnel
Decrease the loads
1. Check whether the UPS system's ventilation is normal
2. Decrease the loads
3. Check whether the fan is functioning normally
4. Clean the filters, if installed
28