FIGURE 35 - SETUP SCREEN

This screen is the top level of the general configura-
tion parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed (12 or 24 hour format). In addition, the
chiller configuration, as determined by the state of the
Microboard Program Jumpers and Program Switches
is displayed. A qualified Service Technician, following
instructions in Service Manual (Form 160.69-M1-C),
establishes this configuration per the desired opera-
tion. This screen also serves as a gateway to more sub-
screens for defining general system parameters.
PROGRAMMABLE
Refrigerant Selection
Access Level Required: SERVICE
Displays R134a or R22 as set by position of SW1-1
On = R134a.
Liquid Type
Displays Water or Brine as set by position of SW1-2
Off = Water.
Chilled Liquid Pump Operation:
Access Level Required: SERVICE
Displays as Standard or Enhanced.
JOHNSON CONTROLS

SETUP SCREEN

Anti-Recycle:
Access Level Required: SERVICE
Selectable as Disabled or Enabled.
Power Failure Restart:
Access Level Required: SERVICE
Selectable as Manual or Automatic.
Motor Drive Type
Access Level Required: SERVICE
Sets the type of Starter that is installed. EM, VSD - 60
Hz, VSD - 50 Hz, or MVVSD.
Coastdown Time
Access Level Required: SERVICE
Sets the Coastdown Time: Standard (150 seconds) or
Enhanced (15 minutes – Steam Turbine applications)
Pre-Run
Access Level Required: OPERATOR
Sets the duration of the system pre-lube: Standard
(50 seconds) or Extended (180 seconds)
Line Frequency
Access Level Required: SERVICE
Sets the Line Frequency: 50 Hz or 60 Hz.