Page 1
AIR-COOLED SCREW LIQUID CHILLERS New Release Form 201.19-NM1 (204) INSTALLATION, OPERATION & MAIN TE NANCE 035-20319-000 YCAS AIR-COOLED LIQUID CHILLERS YCAS0130 THROUGH YCAS0230 STYLE G 028971-G 60 Hz YCAS 2 SYSTEM EPROM 031-01798-001 (STANDARD, BRINE & METRIC MODELS COM BINED)
Page 2
If not found with the manual, the current Revision Sheet containing any applicable revisions, and the manual, can be found on the internet at www.york.com. The Renewal Parts (RP) manual and revision sheet for this equipment can also be found at this internet site.
NOT be installed inside the mi cro pan el. NO external wiring is al lowed to be run through the micro panel. All wir ing must be in ac cor dance with YORK’s pub lished spec i fi ca tions and must be per formed ONLY by qual i fi ed YORK personnel. YORK will not be re spon si ble for dam ag es/problems re sult ing from im prop er con nec tions to the con trols or ap pli ca tion of im prop er con trol sig nals.
Optional Flanges ... 33 REFRIGERANT RELIEF VALVE PIPING ... 33 DUCTWORK CONNECTION ... 33 General Requirements ... 33 ELECTRICAL CONNECTION ... 34 POWER WIRING... 34 STANDARD UNITS WITH MULTI POINT POWER SUPPLY WIRING ... 34 FORM 201.19-NM1 (204) YORK INTERNATIONAL...
Page 6
8.5 EEV Operation ... 173 8.6 EEV Programming ... 175 8.7 EEV Troubleshooting ... 176 8.8 Condenser Fan Control... 177 8.9 Service Mode: Unit Setup ... 179 8.10 Sensor Calibration Charts... 185 8.11 Control Inputs/Outputs ... 186 8.12 ISN Control ... 189 YORK INTERNATIONAL...
Page 7
TABLE 5 – Service Mode Programmable Values ...179 YORK INTERNATIONAL SECTION 11 - TROUBLE SHOOTING TROUBLESHOOTING GUIDE ... 200 LIMITED WARRANTY YORK AMERICAS ENGINEERED SYSTEMS ... 202 WARRANTY ON NEW EQUIPMENT ... 202 WARRANTY ON RECONDITIONED OR REPLACEMENT MATERIALS ... 202 TEMPERATURE CONVERSION CHART...
Page 8
LOCATION...73 FIG. 22C – POWER PANEL (SYSTEM #2) COMPONENT LOCATIONS... 74 LIST OF FIGURES FIG. 23 – MODEL YCAS0130 - 0180 DIMENSIONS (ENGLISH) ... 82 FIG. 25 – MODEL YCAS0200 - YCAS0230 DIMENSIONS (ENGLISH) ... 86 FIG. 26 – MODEL YCAS0200 - YCAS0230 DIMENSIONS (SI)...
WARRANTY York International warrants all equipment and ma te ri als against defects in workmanship and materials for a pe ri od of eighteen months from deliveryunless extended warranty has been agreed upon as part of the contract.
This manual and any other document supplied with the unit, are the property of YORK which reserves all rights. They may not be reproduced, in whole or in part, with out prior written authorization from an authorized YORK representative.
Use of gloves and safety glass es are, however, recommended when working on the unit. The build up of refrigerant vapor, from a leak for ex- YORK INTERNATIONAL FORM 201.19-NM1 (204) am ple, does pose a risk of asphyxiation in confi ned or enclosed spac es and attention should be given to good ven ti la tion.
10 Option Box FIG. 1 – COMPONENT LOCATIONS INTRODUCTION YORK YCAS chillers are designed for water or wa- ter-glycol cooling. All units are designed to be lo cat ed outside on the roof of a building or at ground level.
FIG. 2 – SCREW COMPRESSOR YORK INTERNATIONAL The compressor is lubricated by removing oil from the refrigerant using an external oil separator. The pres sur ized oil from the oil separator is then cooled in the condenser coils and piped back to the compressor for lubrication.
fl ows to the condenser for cooling before returning to the compressor. The oil (YORK “L” oil – a POE oil used for all re frig - er ant applications), which fl ows back into the com- pres sor through a replaceable 0.5 - 3.0 micron oil fi...
The software is stored in non-volatile memory (EPROM) to eliminate chiller failure due to AC power failure. The Programmed Setpoints are stored in lithium battery backed memory. YORK INTERNATIONAL FORM 201.19-NM1 (204) Motor Current Protection The microprocessor motor protection provides high...
"ON" switches equals the overload setting. It is recommended that a YORK Ser- vice Tech ni cian or the YORK fac to ry be con sult ed before chang ing these settings for any rea son, since dam- age to the com pres sor could re sult.
An unloaded compressor condition occurs when any measured half line current is less than the “Operating YORK INTERNATIONAL Current.” A current imbalance exceeding an unloaded level of 25% will result in the motor pilot circuit being de-energized.
PHASE 0150 SYS. 1 0150 SYS. 2 0160 0170 SYS. 1 0170 SYS. 2 * Indicates one lead/phase through motor protector. MO TOR PROTECTOR DIP SWITCH SETTINGS ON MP (“1” INDICATES ON) DISPLAY HA XXX FORM 201.19-NM1 (204) YORK INTERNATIONAL...
Page 19
YCAS STYLE G, ACROSS-THE-LINE – 60 HZ CHILLER MODEL VOLT LEADS NAMEPLATE CODE PHASE SYS. 1 SYS. 2 * Indicates one lead/phase through motor protector YORK INTERNATIONAL MO TOR PROTECTOR DIP SWITCH SETTINGS ON MP (“1” INDICATES ON) DISPLAY HA XXX FORM 201.19-NM1 (204)
Page 20
PHASE 0150 SYS. 1 0150 SYS. 2 0160 0170 SYS. 1 0170 SYS. 2 * Indicates one lead/phase through motor protector. MO TOR PROTECTOR DIP SWITCH SETTINGS ON MP (“1” INDICATES ON) DISPLAY HA XXX FORM 201.19-NM1 (204) YORK INTERNATIONAL...
Page 21
YCAS STYLE G, WYE DELTA START – 60 HZ CHILLER MODEL VOLT LEADS NAMEPLATE CODE PHASE SYS. 1 SYS. 2 * Indicates one lead/phase through motor protector. YORK INTERNATIONAL MO TOR PROTECTOR DIP SWITCH SETTINGS ON MP (“1” INDICATES ON) DISPLAY HA XXX FORM 201.19-NM1 (204)
• Status of: evaporator heater, condenser fans, load and unload timers, chilled water pump. • “Out of range” message. • Up to 6 fault shut down conditions. The standard display language is English, with 4 other languages available. YORK INTERNATIONAL...
Printed circuit board to accept 4 to 20mA, 0 to 10VDC, or dry contact closure input from the BAS. A YORK ISN Building Automation System can pro- vide a Pulse Width Modulated (PWM) signal direct to the standard control panel via the standard on-board RS485 port.
Housings de- signed to withstand a minimum 1.0 g accelerated force in all directions to 2" (51 mm). Level ad just able, de fl ec tion may vary slightly by application. (Field- mount ed). YORK INTERNATIONAL...
Major damage must be reported immediately to your lo cal YORK representative. MOVING THE CHILLER Prior to moving the unit, ensure that the installation...
4-3/4" (120 mm) wide at the con tact points. This will allow vibration isolators to be fi tted if required. YORK INTERNATIONAL INSTALLATION Any ductwork or attenuators fi tted to the unit must not have a total static pressure resistance, at full unit air fl...
2. This assembly reduces compressor noise by isolating the compressor from the base rails. DO NOT remove the four 3/8" bolts, 3, mounting the corner brackets, 2, to the frame rails. YORK INTERNATIONAL LD09131...
150 PSIG (10 bar) (optional 300 PSIG) working pres sure and hav ing a 1" N.P.T. con- nection can be obtained from YORK as an ac ces so ry for the unit. Al ter na tive ly a dif fer en tial pres sure switch sited across an orifi...
Aerated, brackish or salt water is not recommended for use in the water system(s). YORK recommends that a wa ter treatment specialist is consulted to determine the proposed water composition will not affect the evap o - ra tor materials of carbon steel and copper.
YORK INTERNATIONAL It is recommended that a piece of pipe is fi tted to each valve and directed so that if the valve is activated, the release of high pressure gas and liquid cannot be a dan ger or cause injury.
FORM 201.19-NM1 (204) All sources of supply to the unit must be taken via a common point of iso- la tion (not sup plied by YORK). STANDARD UNITS WITH MULTI POINT POWER SUPPLY WIRING Standard units require two 3-phase sep a rate ly fused 3- wire supplies plus a ground per re frig er ant system.
(Figs. 13 and 14) for No. 2 Sys tem. SYSTEM INPUTS Flow Switch A chilled water fl ow switch, (either by YORK or others) MUST be installed in the leaving water piping of the evaporator. There should be a straight horizontal run of at least 5 diameters on each side of the switch.
Installation FORM 201.19-NM1 (204) POWER PANEL LAYOUTS (TYPICAL) 028972-G 028973-G OPTIONAL DISCONNECT SWITCH OPTIONAL CIRCUIT BREAKER SWITCH (WYE-DELTA - TYPICAL) ACROSS THE LINE - TYPICAL) FIG. 9 – POWER PANEL SECTION YORK INTERNATIONAL...
OPTION PANEL LAYOUT (TYPICAL) FIG. 10 – OPTION PANEL SECTION YORK INTERNATIONAL FORM 201.19-NM1 (204) LOGIC PANEL OPTION PANEL WITH SINGLE POINT TERMINAL BLOCK (OPTIONAL) 00246VIP...
System No. 1 Run System No. 1 Alarm Contacts System No. 2 Run Chilled Liquid Circulating Pump Start System No. 2 Alarm Contacts Chiller Run Isolator Auxiliary Interlock FORM 201.19-NM1 (204) 028977-G CONNECTION POINTS FOR EMERGENCY STOPS LD03502 YORK INTERNATIONAL...
Compressor Oil To add oil to a circuit - connect a YORK hand oil pump (Part No. 470-10654-000) to the 1/4" oil charging valve on the oil separator piping with a length of clean hose COMMISSIONING or cop per line, but do not tighten the fl...
Verify a chilled water fl ow switch is cor rect ly fi tted in the customer’s pipework on the evaporator outlet, and wired into the control panel correctly using shielded YORK INTERNATIONAL FORM 201.19-NM1 (204) cable. There should be a straight run of at least 5 pipe di am e ters on either side of the fl...
OFF the ‘SYS 1’ switch on the main panel microprocessor board and repeat the pro cess for each subsequent system. When all run cor rect ly, stop the unit, switch all applicable switch es to the ‘ON’ po si tion and restart the unit. YORK INTERNATIONAL...
Page 45
FORM 201.19-NM1 (204) This page intentionally left blank. YORK INTERNATIONAL...
Op er a tion GENERAL DESCRIPTION The units are designed to work independently, or in con junc tion with other equipment via a YORK ISN build ing management system or other automated con- trol sys tem. When operating, the unit controls monitor...
Page 47
FORM 201.19-NM1 (204) This page intentionally left blank. YORK INTERNATIONAL...
Technical Data FLOW RATE AND PRESSURE DROP CHARTS EVAPORATOR WATER PRESSURE DROP (ENGLISH UNITS) YCAS0130 - 0230 100.00 10.00 1.00 Flow, GPM MODEL NUMBER YCAS 0130, 0140 0150, 0160, 0170, 0180, 0200, 0210, 0230 Pressure Conversion : Ft H20 = 2.3 x PSI FIG.
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK offi ce for application requirements. 2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK offi ce for application guidelines. 3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
Page 50
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK offi ce for application requirements. 2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK offi ce for application guidelines. 3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
Water Side Pressure, PSIG Maximum Refrigerant Side Pressure, PSIG Minimum Chilled Water Flow Rate, GPM Maximum Chilled Water Flow Rate, GPM Water Connections, inches Optional 300 PSIG Waterside available YORK INTERNATIONAL PHYSICAL DATA ENGLISH UNITS MODEL NUMBER YCAS 0130EC 0140EC...
HIGH PRESS. FANS OPTION 2 LOW NOISE (4 PL) ELECTRICAL THREE PHASE 60 Hz (V) * Maximum Ambient w/ High Ambient Kit is 130°F. YORK INTERNATIONAL OPERATING LIMITATIONS – SI UNITS 40.1 LEAVING CHILLED LIQUID TEMP ( °C) CHILLED WATER TEMP DIFFERENCE ( °C)
Page 59
MODEL COMPRESSOR DATA VOLTS YCAS X-LRA 0130EC 0140EC 0150EC 0160EC 0170EC 0180EC 0200EC 0210EC 0230EC YORK INTERNATIONAL ELECTRICAL DATA SYSTEM #1 FAN DATA COMPRESSOR DATA 11, 12 (EA.) (EA) 19.0 15.2 19.0 15.2 19.0 15.2 19.0 15.2 19.0 15.2 19.0 15.2...
Page 61
MAXIMUM kW AND AMPERAGE VALUES FOR DXST COMPRESSORS DXS45LA – MOTOR CODE A (B5N, B5E, B6N, B6E) VOLTAGE CODE- MAX kW MAX AMPS YORK INTERNATIONAL ELECTRICAL DATA COMPRESSOR MODEL AND VOLTAGE CODE DXS36LA – MOTOR CODE A (A5N, A5E, A6N, A6E) FORM 201.19-NM1 (204) DXS24LA –...
13. Group Rated breaker must be HACR type for cU.L. Machines. ELECTRICAL NOTES MAX DUAL (MAX LOAD ELEMENT CURRENT) FUSE SIZE FORM 201.19-NM1 (204) VOLTAGE CODE -17 = 200-3-60 -28 = 230-3-60 -40 = 380-3-60 -46 = 460-3-60 -58 = 575-3-60 NON-FUSED DISCONNECT SWITCH SIZE YORK INTERNATIONAL...
Page 63
FORM 201.19-NM1 (204) This page intentionally left blank. YORK INTERNATIONAL...
Transient Voltage Suppression Terminal Block for Customer Connections Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 Terminal Block for YORK Connections Only Wiring and Components by YORK Optional Equipment Wiring and/or Components by Others FORM 201.19-NM1 (204)
Technical Data FORM 201.19-NM1 (204) ELEMENTARY DIAGRAM LD09234 FIG. 19 – ELEMENTARY DIAGRAM – ACROSS-THE-LINE START YORK INTERNATIONAL...
Page 67
BAS in puts on ter mi nals 13 - 19 or TB3, or any oth er ter mi nals, must be sup- pressed with a YORK P/N 031- 00808-000 sup pres sor across the re lay/con tac tor coil.
Transient Voltage Suppression Terminal Block for Customer Connections Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 Terminal Block for YORK Connections Only Wiring and Components by YORK Optional Equipment Wiring and/or Components by Others FORM 201.19-NM1 (204)
Technical Data FORM 201.19-NM1 (204) ELEMENTARY DIAGRAM LD09234 FIG. 22 – ELEMENTARY DIAGRAM – WYE-DELTA START YORK INTERNATIONAL...
Page 71
BAS inputs on ter mi nals 13 - 19 or TB3, or any oth er ter mi nals, must be sup- pressed with a YORK P/N 031- 00808-000 sup pres sor across the re lay/con tac tor coil.
Site re stric tions may com pro mise minimum clearances in di cat ed be low, re sult ing in un pre dict able air fl ow patterns and possible di min ished per for mance. YORK’s unit con trols will optimize op er a tion without nuisance high pres sure safe ty cut out;...
Page 83
DIMENSIONS – YCAS0130 - YCAS0180 (ENGLISH) CENTER OF GRAVITY (Alum.) YCAS 0130 101.3" 0140 101.3" 0150 106.7" 0160 107.0" 0170 107.0" 0180 107.0" YORK INTERNATIONAL CENTER OF GRAVITY (Cop per) YCAS 44.4" 37.8" 0130 103.5" 44.4" 44.4" 37.8" 0140 103.5"...
Site re stric tions may compromise minimum clearances indicated below, resulting in un pre dict able air fl ow patterns and possible diminished performance. YORK’s unit controls will optimize op er a tion without nuisance high pressure safety cutout;...
Page 85
DIMENSIONS – YCAS0130 - YCAS0180 (SI) $"& $"& CENTER OF GRAVITY (Alum.) YCAS 0130 2573.0 1127.8 960.1 0140 2573.0 1127.8 960.1 0150 2710.2 1087.1 919.5 0160 2717.8 1092.2 919.5 0170 2717.8 1092.2 919.5 0180 2717.8 1092.2 919.5 YORK INTERNATIONAL CENTER OF GRAVITY (Cop per)
Site re stric tions may compromise minimum clearances indicated below, resulting in un pre dict able air fl ow patterns and possible di min ished performance. YORK’s unit controls will optimize op er a tion without nui sance high pressure safety cutout;...
Page 87
DIMENSIONS – YCAS0200 - YCAS0230 (ENGLISH) CENTER OF GRAVITY (Alum.) YCAS 0200 119.4" 0210 119.4" 0230 119.4" YORK INTERNATIONAL CENTER OF GRAVITY (Copper) YCAS 43.2" 38.0" 0200 122.3" 43.3" 43.2" 38.0" 0210 122.3" 43.3" 43.2" 38.0" 0230 122.3" 43.3" FORM 201.19-NM1 (204) LD03749 41.0"...
Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air fl ow pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout;...
Page 89
$"& CENTER OF GRAVITY (Alum.) YCAS 0200 3032.8 1097.3 965.2 0210 3032.8 1097.3 965.2 0230 3032.8 1097.3 965.2 YORK INTERNATIONAL CENTER OF GRAVITY (Copper) YCAS 0200 3106.4 1099.8 1041.4 0210 3106.4 1099.8 1041.4 0230 3106.4 1099.8 1041.4 FORM 201.19-NM1 (204)
(2 m) (1.3 m) LD07011 NOTES: 1. No obstructions allowed above the unit. 2. Only one adjacent wall may be higher than the unit. 3. Adjacent units should be 10 feet (3 meters) apart. FIG. 27 – CLEARANCES YORK INTERNATIONAL...
Page 94
TYPE R OR RD IF BOLTING IS PREFERRED– Type R or RD mountings are furnished with a tapped hole in the center. This enables the equipment to be bolted securely to the mounting. LD04033 3" 1/2" 5" 9/16" 3/8" YORK INTERNATIONAL 29517A...
Page 95
COPPER FIN CONDENSER COILS WEIGHT DISTRIBUTION BY MODEL (KGS) YCAS 0130 0140 0150 0160 0170 0180 0200 1,052 1,077 0210 1,059 1,087 0230 1,060 1,092 YORK INTERNATIONAL Copper Fin Condenser Coils 1,735 1,450 1,165 1,754 1,465 1,177 1,869 1,671 1,472 1,875 1,685 1,495 1,900 1,710 1,519...
2-531 1-553 1-552 1-551 AWMR-1-XXX DIMENSIONS - In. AWMR-1 10-1/2 50-553 11NC AWMR-2 50-553 10NC FIG. 31 – TYPE AWMR ISOLATOR DETAILS YORK INTERNATIONAL Copper Fin Condenser Coils 1-553 1-552 1-551 1-532 1-553 1-552 1-551 1-532 1-553 1-552 1-552 1-552...
Page 98
TYPE R OR RD IF BOLTING IS PREFERRED– Type R or RD mountings are furnished with a tapped hole in the center. This enables the equipment to be bolted securely to the mounting. 3" 1/2" 5" 9/16" 3/8" YORK INTERNATIONAL 29517A LD04033...
Page 99
ALUMINUM FIN COIL WEIGHT DISTRIBUTION BY MODEL (KGS) YCAS 0130 0140 0150 0160 0170 0180 0200 1,052 1,077 0210 1,059 1,087 0230 1,060 1,092 YORK INTERNATIONAL Aluminium Fin Condenser Coils with Silencer Kit 1,735 1,450 1,165 1,754 1,465 1,177 1,869 1,671 1,472 1,875 1,685 1,495 1,900 1,710...
0230 2-531 1-553 1-552 1-551 AWMR-1-XXX DIMENSIONS - In. AWMR-1 10-1/2 50-553 11NC AWMR-2 50-553 10NC FIG. 33 – TYPE AWMR ISOLATOR DETAILS YORK INTERNATIONAL 1-553 1-552 1-551 1-532 1-553 1-552 1-551 1-532 1-553 1-552 1-552 1-552 1-553 1-552 1-552...
Page 102
TYPE R OR RD IF BOLTING IS PREFERRED– Type R or RD mountings are furnished with a tapped hole in the center. This enables the equipment to be bolted securely to the mounting. 3" 1/2" 5" 9/16" 3/8" YORK INTERNATIONAL 29517A LD04033...
0230 2-532 2-553 1-553 1-551 AWMR-1-XXX DIMENSIONS - In. AWMR-1 10-1/2 50-553 11NC AWMR-2 50-553 10NC FIG. 35 – TYPE AWMR ISOLATOR DETAILS YORK INTERNATIONAL 1-553 1-552 1-552 1-531 1-553 1-552 1-552 1-531 1-553 1-553 1-553 1-553 1-553 1-553 1-553...
Page 106
TYPE R OR RD IF BOLTING IS PREFERRED– Type R or RD mountings are furnished with a tapped hole in the center. This enables the equipment to be bolted securely to the mounting. 3" 1/2" 5" 9/16" 3/8" YORK INTERNATIONAL 29517A LD04033...
Complete piping and fi ll equipment with wa ter, re frig er ant, etc. YORK INTERNATIONAL RESTRAINED MOUNTINGS Turn leveling bolt of fi rst isolator four full rev o - lu tions and proceed to each mount in turn.
Me di um pres sure vapor then returns to the compressor. The subcooled refrigerant then passes through the ex pan sion valve where pressure is reduced and fur ther cool ing takes place before return- ing to the evaporator. FORM 201.19-NM1 (204) LD09428 YORK INTERNATIONAL...
CHILLED WATER FLOW MAJOR COMPONENTS COMP COMPRESSOR CONDENSER COIL COOLER OIL COOLER COIL OIL SEPARATOR FIG. 37 – PROCESS AND INSTRUMENTATION DIAGRAM YORK INTERNATIONAL COMP MICROPROCESSOR CONTROL FUNCTIONS FORM 201.19-NM1 (204) SYSTEM COMPONENTS EXPANSION VALVE, THERMOSTATIC ELECTRONIC SOLENOID VALVE BALL VALVE...
OIL PRESSURE OIL TEMPERATURE SUCTION PRESSURE COMPRESSOR CAPACITY CONTROL VALVE CRANK CASE HEATER EVAPORATOR HEATER HIGH PRESSURE CUT-OUT SUCTION TEMPERATURE SENSOR REFRIGERANT FEED TEMPERATURE SENSOR (R407C only) COMPRESSOR MOTOR TERMINAL BOX COMPRESSOR FORM 201.19-NM1 (204) 1-BOP 3-BOP LD07012 YORK INTERNATIONAL...
COMPRESSOR COMPONENTS SUCTION GAS IN MOTOR TERMINALS STATOR LOCKING BOLT LIFTING LUG THREADED HOLE HEATER FIG. 39 – COMPRESSOR COMPONENTS YORK INTERNATIONAL LIFTING LUG THREADED HOLE OIL PRESSURE TRANSDUCER LOCATION ROTOR CASE ECONOMIZER GAS IN DISCHARGE CASE EVACUATION PORT OIL INLET...
9. Program the Daily Schedule start and stop times. 10.Check the Factory Service Mode programming values, (See Section 8.9) assure they are correct, and record the values below: Refrigerant Type = __________________________ R407C Chiller Type = ________________________ Unit Type = _______________________________ FORM 201.19-NM1 (204) _________________________ YORK INTERNATIONAL...
This should be of no con cern and lasts for only a short time. YORK INTERNATIONAL 4. Check the system operating parameters. Do this by selecting various displays such as pres sures and tem per a tures.
°F (°C) is ready to be placed into operation. FORM 201.19-NM1 (204) 90°F (32°C) to Temp - 78°F (26°C) 12°F (6°C) SYS 1 SYS 2 PSIG (kPa) °F (°C) (°C) °F °F (°C) YORK INTERNATIONAL...
Page 121
FORM 201.19-NM1 (204) This page intentionally left blank. YORK INTERNATIONAL...
Program Key - see Section 8 This key is used for display and programming of the chiller operational settings and limits. FORM 201.19-NM1 (204) DISPLAY SETPOINTS CLOCK 29023A PROGRAM & SETUP KEY YORK INTERNATIONAL...
1. INTRODUCTION & PHYSICAL DESCRIPTION 1.1 GENERAL The YORK Screw Chiller Control Panel is a mi cro pro - ces sor based control system fi tted to YCAS liq uid chill- ers. It is capable of multi-re frig er ant system con trol to maintain chilled liquid tem per a ture within pro grammed limits and to provide safety control of the chill er.
Mi cro pro ces sor through address lines. Signals routed through the I/O Expansion Board in clude Dis charge Temperature, Motor Protector Current Transformer outputs (motor current signals from the 2ACE Module), and Oil Temperature. YORK INTERNATIONAL...
High voltage cir- cuit ry will still be en er gized from the high volt age sup ply. YORK INTERNATIONAL FORM 201.19-NM1 (204) REMOVING 115VAC power to CB3 or open ing CB3 removes pow er from the evap o ra tor heat ers.
Page 126
Always record the number displayed on the module display before removing power. Ad di tion al de tails on the Mo tor Pro tec tion Mod ule can be found on page 16. YORK INTERNATIONAL...
SWITCHES PLACED IN THE ON POSITION ADD TO EQUAL THE OVERLOAD SETTING VALUE. FOR EXAMPLE, WITH 2 ON AND 128 ON, DISPLAY WILL FLASH HA130. FIG. 45 – MOTOR PROTECTION MODULE YORK INTERNATIONAL SIDE VIEW TOP VIEW TOP VIEW NUMERICAL VALUES SIDE VIEW FORM 201.19-NM1 (204)
If an in duc tive device (re lay, contactor) is sup ply ing these con tacts, the coil of the de vice must be sup pressed with a sup pres sor YORK Part Number 031- 00808-000 across the in duc tive coil. Remote Current Reset...
Page 129
If an in duc tive de vice (re lay, contactor) is sup ply ing these con tacts, the coil of the de vice must be sup pressed with a sup pres sor YORK Part Num ber 031-00808-000 across the in duc tive coil.
NOTE : Dimple is positioned at top edge (3A) Dip Switch Set (8 switches) System Switches S2 = System 1 S3 = System 2 S2 to S5 S4 = System 3 S5 = System 4 FORM 201.19-NM1 (204) 028979-G YORK INTERNATIONAL...
Econ o miz er Liquid Supply Solenoid Valve is de-energized. The compressor continues to op er ate until it either pumps down to the Remote evaporator applications equipped with thermostatic TXV and Liquid Line solenoid will also pump down on shutdown. YORK INTERNATIONAL...
RC sup pres sor YORK Part Num ber 031- 00808-000 across the in duc tive coil. Fail ure to in stall sup pres sors will result in nui sance faults and pos si ble damage to the chill er.
The second timer assures that a minimum of 3 minutes elapses from the time the economizer turns off to the next time it is called to turn on again. YORK INTERNATIONAL...
C O M P R U N N I N G S Y S C O M P R U N N I N G This message indicates that the respective compressor is running due to demand. YORK INTERNATIONAL O F F...
Logic Section of the control panel is open. Whenever the contact is open, the No Run Per mis sive message will be displayed and the in di cat ed sys tem will not run. YORK INTERNATIONAL System Loading Requirement: S Y S...
YORK INTERNATIONAL ning of the chiller is not economical compared to the use of “free” cooling techniques (see also Section 8.2 / Low Ambient Temperature Cutout [page 168]).
225°F (107°C) for more than 3 sec onds, the compressor will shut down. YORK INTERNATIONAL Low Suction Pressure Cutout: S Y S D I F F...
Page 142
This may result from loss of re frig er ant, a de- fective contactor, power problems, or from a compressor that is not pumping due to a mechanical malfunction. YORK INTERNATIONAL C U R R C U R R...
Evaporator Inlet Refrigerant Temp Sen sors to mon i tor evaporator inlet refrigerant tem per a ture on each system. These sensors are only installed on R- YORK INTERNATIONAL 407C units. If the refrigerant temperature falls below 20°F (11.1°C) in water cooling mode, the system will be shut down.
To the mi cro pro ces sor, STEP 0 = fully unloaded and STEP 75 = fully loaded. YORK INTERNATIONAL Slide valve position is AP PROX I MATE and should be used for ref er ence only.
(YCAS). The switch MUST always be in the CLOSED position. Incorrect programming may cause damage to the chiller. YORK INTERNATIONAL FORM 201.19-NM1 (204) Dip Switch Physical Location and Setting “OPEN” Position: Left side of switch pushed in “CLOSED”...
After scrolling through the data, the display returns to the status mes sage. The following keys can be scrolled using the Function Key: Chilled Liquid Temps, System # Data, Motor Cur- rent and Options. YORK INTERNATIONAL SETTING Glycol Cooling YCAS Motor Current...
The data is stored in temporary memory, then trans mit ted from the microprocessor to the remote print er. As the data is transmitted it is erased from the memory. YORK INTERNATIONAL 4. PRINT KEYS Information available using the Operating Data key is de- scribed in the following sections.
Page 150
S U C T = 3 4 . 7 ° F = 1 0 . 5 ° F D S C H = 1 2 9 ° F = 6 2 . 8 ° F S T E P YORK INTERNATIONAL...
The follow text shows a typical example printout ob tained by pressing the Operating Data key with an op tion al printer attached. In this case, an example is shown for a YCAS 2 System Chiller. YORK INTERNATIONAL CORPORATION MILLENNIUM SCREW CHILLER SYS 1 SYS 2...
S H U T D O W N 5 : 5 9 A M FORM 201.19-NM1 (204) S A F E T Y S H U T - N O . 1 O C C U R R E D N O V YORK INTERNATIONAL...
Page 153
D I S A B L E D This message indicates whether heat recovery is dis- abled or enabled. (HEAT RECOVERY MUST BE DISABLED) YORK INTERNATIONAL S 1 - 7 E X P A N S I O N This message indicates whether electronic or thermo- static expansion valve is selected.
Page 154
C O M P R E S S O R R U N T I M E D - H - M - S M O T O R C U R R E N T 7 8 % F L A YORK INTERNATIONAL...
Page 155
T E M P This message, which is only displayed if the unit is in R-407C mode, indicates the refrigerant temperature at the inlet of the evaporator. YORK INTERNATIONAL P S I G S Y S P S I G...
6 faults. An example of the HISTORY Printout is shown be- low: YORK INTERNATIONAL CORPORATION MILLENNIUM SCREW CHILLER SAFETY SHUTDOWN NUMBER 1 SHUTDOWN @ 3:56PM 29 SEP 02 SYS 1...
If this is not done, the new values entered will be lost and the original values will be returned. YORK INTERNATIONAL 5. ENTRY KEYS The Enter key is also used to scroll through available data when using the Program or Set Schedule/Holiday keys.
This is accomplished by analyzing the tem- per a ture error and the rate of change to determine the amount of loading necessary to cool the chilled liq uid YORK INTERNATIONAL (User ac- cept able leaving...
Page 159
Load Timers are always set at 10 seconds be tween changes. • Unload Timers are set at 5 seconds between chang- YORK INTERNATIONAL Slide Valve Position A slide valve position (S V STEP), under the keypad system keys, of 75 indicates that the compressor is ful ly loaded.
Page 160
Timer Counts to "0" > 70 % > 80 % > 90 % > 95 % In the case of Saturated suction temperature, the micro limits loading based on saturated suction temperature dropping toward the point of unloading. In the water YORK INTERNATIONAL...
Page 161
In the water cooling mode, the saturated suction tempera- ture unload point is 24ºF (-4.42ºC) In the glycol cooling YORK INTERNATIONAL mode, the saturated suction temperature unload point is equal to the leaving chilled liquid setpoint -11ºF (6.1ºC).
Press ENTER to move on to the hour part of the display. Next, key in the time (hours/minutes) using a leading YORK INTERNATIONAL 7. CLOCK KEYS “0” for times before 10 o’clock. e.g. 08:31. The cursor will then advance to the AM/PM designation.
3 seconds, the system will shut down. Normally, air-cooled chillers, such as YCAS chillers, FORM 201.19-NM1 (204) 29023A R A N G E P R E S S U R E 3 9 5 . 0 P S I G YORK INTERNATIONAL...
Page 167
YORK INTERNATIONAL After the compressor starts, and the pump down cycle is completed (pump down to cutout or 30 seconds, which- ev er comes fi...
Page 168
105% of full load current, this feature will protect against ex ces sive current causing compressor shutdown due to extremely high ambient, high chilled liquid tem- per a ture, and condenser malfunction caused by dirt or fan prob lems. YORK INTERNATIONAL T E M P F L A...
Page 169
To program the Anti-Recycle Time, key in the required setting and press the Enter key to store the value into memory and scroll to the next display. YORK INTERNATIONAL FORM 201.19-NM1 (204) S U C T I O N S U P E R H E A T S E T P O I N T = 1 2 .
FORM 201.19-NM1 (204) M O D E * * * * S E T P O I N T S N O, O P T I O N S S E T V A L U E S YORK INTERNATIONAL...
Page 171
Anti Recycle Time Local / Remote Mode Units Mode Lead / Lag Control Mode Power Failure Restart Mode Motor Current Averaging Cutout Suction Superheat Setpoint YORK INTERNATIONAL Mode Low Limit High Limit 200 PSIG 399 PSIG 13.8 Bars 27.5 Bars...
FORM 201.19-NM1 (204) setpoint. The refrigerant fl ow direction is designated by an arrow on the expansion valve body. There are two safeties associated with the EEV; Low Superheat Cutout and Sensor Failure Cutout. 24 VAC HEAT MOTOR YORK INTERNATIONAL LD09132...
This PWM output is the percentage of a 1 second pe ri od that the 24VAC heat motor power signal is energized. YORK INTERNATIONAL 8.5 EEV OPERATION MOP FEATURE The controller also has an MOP feature (Max i mum Op- erating Pressure) that overrides superheat con trol when the MOP setpoint is exceeded.
The Expansion Valve type selection is viewable un der the OP TIONS key. TABLE 2 – PROGRAMMABLE VALUES TABLE (MINIMUM/MAXIMUM) PROGRAM VALUE SUPERHEAT SETPOINT YORK INTERNATIONAL 8.6 EEV PROGRAMMING PROGRAM MODE DISPLAYS The following value is programmable under the PRO- GRAM key (See Table 2).
· Verify that the EEV heat motor is properly in su lat ed. · For units with Hot Gas Bypass installed, check that the Hot Gas Bypass valve is set correctly. · For glycol units, verify that the glycol % is cor rect. YORK INTERNATIONAL...
Setup values may be checked in the Service Mode by pressing the PROGRAM, 5144, and ENTER keys. Table 5 lists the value and the program range that will be accepted. YORK INTERNATIONAL FORM 201.19-NM1 (204) TABLE 5 – SERVICE MODE PROGRAMMABLE VALUES...
Page 181
TABLE 6 – YCAS STYLE G, ACROSS THE LINE START - 60 HZ. (CONT'D) MODEL VOLTAGE CODE SYS 1 SYS 2 * Indicates one lead/phase through motor protector. YORK INTERNATIONAL NO. OF CHILLER LEADS NAMEPLATE PER PHASE OF SYSTEM THRU CT.
Page 183
TABLE 7 – YCAS STYLE G, WYE DELTA START - 60 HZ. (CONT'D) MODEL VOLTAGE CODE SYS 1 SYS 2 * Indicates one lead/phase through motor protector. YORK INTERNATIONAL NO. OF CHILLER LEADS NAMEPLATE PER PHASE OF SYSTEM THRU CT.
Page 184
ENTER key is used to toggle the outputs on and off. Only one output will be allowed on at a time. The only exception will be the compressors which cannot be turned on and off in this mode. FORM 201.19-NM1 (204) YORK INTERNATIONAL...
52-55 56-59 60-63 64-67 68-71 YORK INTERNATIONAL 8.12 ISN CONTROL TRANSMITTED DATA After receiving a valid transmission from the ISN, the unit will transmit either op er a tion al data or history buf- f er data de pend ing on the “History Buffer Re quest” on ISN PAGE 06.
Page 190
*Sys 2 Operatioanal Code *Sys 2 Fault Code Sys 1 Slide Valve Step Sys 1 Condenser Fan Stages Running (0-6) Sys 2 Slide Valve Step Sys 2 Condenser Fan Stages Running (0-6) Lead Compressor Number Debug Code FORM 201.19-NM1 (204) YORK INTERNATIONAL...
Page 191
170-173 174-177 178-181 182-185 186-189 190-193 Digital YORK INTERNATIONAL DXST Chiller Data Leaving Chilled Liquid Setpoint Low Leaving Chilled Liquid Temp Cutout Sys 1 EEV Output % Sys 2 EEV Output % Low Suction Pressure Cutout High Discharge Pressure Cutout...
It is entirely the responsibility of the owner to provide for these regular maintenance requirements and/or en ter into a maintenance agreement with a York In ter na tion al ser vice organization to protect the operation of the unit.
Nor mal ly a ‘minor’ service should be carried out every three to six months and a ‘major’ service once a year. It is recommended that your local YORK Service Cen ter is contacted for recommendations for in di vid u al sites. ON-BOARD BATTERY BACK-UP U17 is the Real Time Clock chip that maintains the date/ time and stores customer programmed setpoints.
Brush fi ns. Clean with mild, low pH cleaner. Check fan motor bearings. Check all connections. Check compressor contactors. Check fan contactors / overloads. Check sensor / transducer calibration. Check motor protectors. Check fan control function. Check ambient cut-out function. YORK INTERNATIONAL...
Other spare parts vary depending on the unit mod el. Review the chiller Renewal Parts Manual or Contact your local YORK Sales and Ser vice Center for in for ma tion (Please quote the unit model num ber and serial number).
Check that the liquid fl ow is stable. Check the voltage to the unloader valve solenoid. Check that the compressor unloads correctly. Check water temp sensor and wiring. Check main supply is stable and within allowable limits. Check for voltage dip on compressor start. YORK INTERNATIONAL...
Page 201
SYS # CURR LIMITING High compressor motor current displayed has activated unloading. (Compressor current un- loading.) YORK INTERNATIONAL FORM 201.19-NM1 (204) ACTION Check for airfl ow restrictions caused by blockages on intake faces of air coils. Check for damaged fi ns/return bends.
REPLACEMENT MATERIALS Except for reciprocating compressors, which YORK war- rants for a period of one year from date of ship ment, YORK warrants reconditioned or re place ment ma te ri als, or start- up ser vic es performed by YORK in connection therewith, against defects in work man ship or material for a period of ninety (90) days from date of shipment.