Schedule Screen; Figure 36 - Schedule Screen - York OPTIVIEW YD Series Manual

Control center centrifugal liquid chillers
Table of Contents

Advertisement

FORM 160.79-O3
ISSUE DATE: 11/09/2018

FIGURE 36 - SCHEDULE SCREEN

The Select key is used to enable the cursor arrows
which are used to highlight the day and the start or stop
time the user wishes to modify. At this point the user
may press the 'a' (Check) key to program the Start /
Stop times for that day.
In order for the Start / Stop combination to be uti-
lized, each Start time must have a corresponding Stop
time which occurs later in the day. The presently pro-
grammed schedule for a given day can be cancelled by
setting both the Start time and Stop time to 12:00 AM.
If the Start time equals the Stop time (with any time
other than 12:00 AM), the chiller is OFF for that day.
If the user desires the chiller to operate continuously
through several days, the Stop time of Day 1 can be
set to 11:59 PM and the Start time of Day 2 can be set
to 12:00 AM. The chiller will not stop but continue to
operate until the stop of Day 2.
The user has the ability to define a standard set of Start
/ Stop times which are utilized every week. The user may
then specify exception Start / Stop combinations for any
day of the week up to 6 weeks in advance. At the end
of each week the schedule for the next week is created
by combining the standard week definition and the next
defined exception week. The schedule is then updated
as each of the exception weeks "shifts down", leaving a
new, blank exception week in the 6th week slot.
JOHNSON CONTROLS

SCHEDULE SCREEN

DISPLAY ONLY
None
PROGRAMMABLE
Select
Access Level Required: OPERATOR
Places a selection box around a start time for a given
day. Use ,,p or q cursor arrows to place the box
around the desired start or stop time for a given day.
Standard Week Start/Stop Times
Access Level Required: OPERATOR
For each day of the week, the user may specify a time
for the chiller to start and a time for the chiller to stop.
The times specified in this entry week will be used as
the default for every week of chiller operation.
Exception Start/Stop Times
Access Level Required: OPERATOR
For each day of the month, the user may specify a time
for the chiller to start and a time for the chiller to stop.
These Start / Stop combinations may be scheduled up
to five (5) weeks in advance and also for the present
week. As each week goes by, the new schedule will
be created for the present week using the Exception
specification in combination with the Standard week
definition, as described above.
SECTION 2 – OPTIVIEW CONTROL CENTER
2
LD27875