Option Modules; Digital I/O Module (Dio) 6Dr4004-6A / -8A - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Technical data

12.10 Option modules

12.10
Option modules
12.10.1

Digital I/O Module (DIO) 6DR4004-6A / -8A

3 digital output current circuits
● Digital output DO1: Terminals 41 and 42
● Digital output DO2: Terminals 51 and 52
● Fault message output: Terminals 31 and 32
● Auxiliary power supply U
● Signal status
High (not addressed)
Low *) (addressed)
*) The status is also Low if the
basic device is faulty or without
a auxiliary power.
● For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
1 digital input current circuit
● Digital input DI2: Terminals 11 and 12, terminals 21 and 22 (jumper)
● Galvanically connected with the
basic device
Signal status 0
Signal status 1
Contact load
● Electrically isolated from the basic
device
Signal status 0
Signal status 1
Internal resistance
250
Without explosion protec‐
tion or suitable for use in
Ex "db" version
6DR4004-8A
≤ 35 V and the current con‐
Aux
sumption is to be limited to
< 25 mA
Conductive, R = 1 kΩ,
+3/-1 % *)
Deactivated, I
R
*) When using in the flame‐
proof enclosure, the cur‐
rent consumption must be
restricted to 10 mA per out‐
put.
-
-
-
With explosion protection
Ex "ia"
6DR4004-6A
-
≥ 2.1 mA
< 60 µA
≤ 1.2 mA
Switching threshold for
supply according to
EN 60947-5-6:
U
= 8.2 V, R
Aux
U
= 15 V DC
i
I
= 25 mA
i
P
= 64 mW
i
C
= 5.2 nF
i
L
= negligibly small
i
Floating contact, open
Floating contact, closed
3 V, 5 μA
≤ 4.5 V or open
≥ 13 V
≥ 25 kΩ
Operating Instructions, 11/2019, A5E00074631-AE
With explosion protection
Ex "ic", "ec", "tb"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching threshold for
supply according to
EN 60947-5-6:
= 1 kΩ
U
= 8.2 V, R
i
Aux
"ic":
U
= 15 V DC
i
I
= 25 mA
i
"ec"/"tb":
U
≤ 15 V DC
n
C
= 5.2 nF
i
L
= negligibly small
i
SIPART PS2 with 4 to 20 mA/HART
= 1 kΩ
i

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents