Siemens SIPART PS2 Series Operating Instructions Manual page 317

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Construction
Weight
Material body
Number of channels, basic electronics:
Climate class
● Storage
● Transport
● Operation
Electrical data
Electrical connection
Current input I
W
● Rated signal range
● Current to maintain the auxiliary power
2-wire connection
● Current to maintain the auxiliary power
● Required load voltage U
● Static destruction limit
Technical specifications for the controller unit is available at Controller (Page 242).
Technical specifications of the Analog Output Module (AOM) are available at Analog Output
Module (AOM) 6DR4004-6J / -8J (Page 251).
Cable data (minimum requirements)
Cable length
Capacity wire / wire
Capacity wire / shield
Inductance
Copper resistance
Insulation conductance
Ambient temperature
Number of poles
● Cable to the control system (min/max)
● Cable to the positioner 6DR5910
Connection
● Cable to the control system (min/max)
● Cable to the positioner 6DR5910
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
(corresponds to Ω at 20 mA)
B
Positioner with remote control electronics
Approx. 1.8 kg
19" slide-in module, 2HM, aluminum
3
According to IEC/EN 60721-3
-25°C to 80°C, 75% at 25°C, without condensation
-25°C to 80°C, 75% at 25°C, without condensation
0°C to 50°C, 75% at 25°C, without condensation
9-pin Sub-D plug
15-pin Sub-D female connector
4 to 20 mA
≥ 3.6 mA
≥ 3.6 mA
6.4 V (= 320 Ω)
± 40 mA
≤ 130 m
≤ 150 nF/km
≤ 200 nF/km
≤ 1 mH/km
≤ 100 Ω/km
≥ 0.5 x 10
S/km
7
-30 ... +80 °C
4 or 9
8 or 15
9-pin Sub-D female connector
15-pin Sub-D male connector
F.2 19" slide-in module
317