Mechanical Limit Switches (Mls) 6Dr4004-6K / -8K - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

5.2.3.4

Mechanical Limit Switches (MLS) 6DR4004-6K / -8K

Supply with hazardous voltage
If you connect the switching contacts of the 6DR4004-8K module to a hazardous voltage,
observe the following safety rules:
1. Isolate the device from power. Use a circuit breaker positioned near the device to do this.
2. Make sure that the device cannot be switched back on inadvertently.
3. Make sure the device is truly isolated from power.
Maximum AC/DC switching voltage with UL approval E344532
Mechanic Limit Switches (MLS) 6DR4004-6K/-8K are approved for use with positioners with
UL approval. The maximum switching voltage in this case is ≤ 30 V AC/DC.
If switching voltages greater than 30 V are connected, the UL approval for the positioner
becomes invalid.
Connection diagram Mechanic Limit Switches (MLS) 6DR4004-6K and -8K
Non-hazardous area
Hazardous area
Mechanic Limit Switches (MLS)
Fault message
Figure 5-10
Mechanic Limit Switches (MLS)
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
DANGER
CAUTION
Limit
Switching amplifier
Switching output
nEx = Non-explosion-proof device version
Connection
5.2 Electrical wiring
85