Diagnostics and troubleshooting
11.2 Diagnostics
11.2.4.5

Diagnostic value '6.HOURS - Number of operating hours'

Display range:
Purpose:
11.2.4.6

Diagnostic value '7.HOURR - Resettable operating hours counter'

Display range:
Purpose:
Description:
11.2.4.7

Diagnostic value '8.WAY - Determined travel'

Condition for
linear actuator:
Display range:
Purpose:
11.2.4.8

Diagnostic value '9.TUP - Travel time up' / '10.TDOWN - Travel time down'

Display range:
Purpose:
216
0 ... 4.29E9
The runtime meter is incremented every hour as soon as electric
auxiliary power is supplied to the positioner.
0 ... 4.29E9
The runtime meter is incremented every hour as soon as electric
auxiliary power is supplied to the positioner. In contrast to Diagnos‐
tic value '6.HOURS - Number of operating hours' (Page 216), this
value can be reset.
In order to minimize the control valve wear resulting from a poor
control quality, it makes sense to optimize the positioner's param‐
eters. You can recognize optimum parameter settings when the
values of the Diagnostic value '44.VEN1R' / '45.VEN2R' (Page 225)
are low. Low values mean that the switching frequency of the posi‐
tioner pneumatics is also low. In order to carry out a comparison
with various parameter settings, determine the number of switching
cycles per hour. To do this, use the values of the Diagnostic value
'44.VEN1R' / '45.VEN2R' (Page 225) and '7.HOURR'. These three
parameters can be reset to enable simpler determination of the
values.
The travel is set in the '3.YWAY' Range of stroke (Page 145) pa‐
rameter.
0 ... 130
This value in mm or ° specifies the travel determined during the
initialization.
0 ... 1000
This value indicates the current UP or DOWN travel time in seconds
determined during the initialization.
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE