Commissioning
7.11 Commissioning part-turn actuators
6. The current potentiometer position is output on the display after 5 seconds:
7. Determine the lower endstop of the actuator.
8. Move the actuator to the desired position using the
9. Press the
following:
Note
Fault message "RANGE"
The selected end position is beyond the permissible measuring range if the "RANGE"
message is output on the display. Correct the settings as follows:
1. Move the friction clutch until the display shows "OK".
2. Press the
3. Move the actuator to another position using the
4. Abort the manual initialization process by pressing the
5. Then return to "P manual mode".
6. Correct the actuator travel and the position detection.
10.Determine the upper endstop of the actuator. Move the actuator to the desired position
using the
11.Press the
12.The initialization process is automatically resumed. Initialization steps "RUN 1" to "RUN 5"
are output in the bottom line of the display. The following display indicates that the
initialization has been completed successfully:
128
button. The current position of the actuator is applied. The display shows the
button.
or
button.
button. The current position of the actuator is applied.
or
button.
or
button.
button.
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE